Infrared Remote Control for EC2
Operating Instructions
GB
HOW TO USE THE REMOTE CONTROL UNIT Access without code
1)HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE CONTROL UNIT TRANSMISSION
•press the 'ENABLE' button to operate the remote control unit;
•the controller's led indicator above the digits flashes and the first parameter - '/C' - is immediately displayed. If the display shows a code different from /C, it is necessary to introduce the access code (see point 5 below).
2)MODIFYING THE MAIN PARAMETERS
• press either the + or - key relative to the parameter you want to modify. The display will show the code of the selected parameter (see the codes of the parameters listed in the Instruction Sheet of the instrument). Press the button again to display the value associated to the selected parameter and
Access with code
5)HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE CONTROL UNIT TRANSMISSION
•press 'ENABLE' to operate the remote control unit;
•all the controllers exposed to the beam of the remote control unit will display their own access code;
•select the access code of the controller whose parameter you intend to modify using the numeric section on the remote control unit. Select the code correctly (if the code of the controller is 05, press 0 and 5).
•the controller's led indicator above the digits flashes and, simultaneously, the code of the first parameter '/C' appears on the display.
•perform the same operations described in point 2) or 3) above.
•press + to increase it;
•press - to decrease it.
The section including directly accessible buttons also comprises 3 buttons that activate/deactivate the function they represent:
DEFROSTING SECTION:
START activates/deactivates a manual defrosting cycle;
evap.tmpdisplays the temperature value measured by the evaporator probe (if present) or the value measured by the second probe (Thermometer
Important: This function is always active. Consequently the temperature measured by the second probe will be always displayed without having to press the 'START' button or select the access code (see point 5 below).
CONTINUOUS CYCLE SECTION:
HOW TO SELECT THE ACCESS CODE
SETTING THE ACCESS CODE
All EC2 controllers have no
•press 'ENABLE' to operate the remote control unit;
•the controller's led indicator above the digits flashes and the first parameter ('/C) appears immediately.
•press to display the H3 parameter;
•press SEL to display its value (default 00);
•press to select the desired value (from 01 to 199);
•press SEL to confirm the new value and display again the H3 code;
•press PRG to memorize the access code and exit the procedure.
REMOVING THE CODE
C.cycle. activates a continuous cycle;
•see point 4 below to exit the programming procedure.
3)HOW TO MODIFY THE PARAMETERS NOT DIRECTLY INDICATED BY A SPECIFIC BUTTON
The other parameters - not directly associated to a specific button on the remote control unit - can be easily modified as follows:
•perform the same operations described in point 1 above until the first parameter '/C' appears on the display;
3.1press either or
until the display shows the parameter you want to modify;
•press SEL to display the value of the selected parameter;
•press either or
to increase/decrease its value;
•press SEL to confirm temporarily the new value and display again the code of the parameter;
•to modify another parameter repeat the operations described above starting from point 3.1;
•see point 4 below to exit the programming procedure.
4)HOW TO EXIT THE PROGRAMMING PROCEDURE
•press PRG to exit and memorize all modifications;
•press ESC to exit without memorizing the previous modifications;
•do not press any button for at least 60 seconds (TIME OUT). In this way the previous modifications will be cancelled.
•repeat the operations described above and give the H3 parameter the value 00 (H3=00). In this way you can program your controller/s without selecting the access code.
WHAT TO DO IF THE REMOTE CONTROL DOESN'T WORK
•check that the remote control is equipped with batteries aligned correctly;
•replace spent or weak batteries;
•check that there are no obstacles between controller and transmitter;
•periodically clean the transmitter and the controller with a soft cloth;
•remember that the remote control's usable range is within 3 meters away from the controller.
•in case parameters are accessible but the user is not allowed to change values, verify "H2" parameter (refer to the USER manual)
MODELS
There are several versions available, in different languages:
Language | Type | Order Nr. |
English | EC2- IRE | 804 345 |
German | EC2- IRD | 804 346 |
French | EC2- IRF | 804 347 |
Spanish | EC2- IRS | 804 348 |
Italian | EC2- IRI | 804 349 |
Emerson Electric GmbH & Co.OHG is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information given herein is based on technical data and tests which ALCO CONTROLS believes to be reliable and which are in compliance with technical knowledge of today. It is intended only for use by persons having the
appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of ALCO'S control we cannot assume any liability for results obtained or damages occurred due to improper application.
This document replaces all former versions.
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 -
www.eCopeland.com/alcoliterature.cfm
Replacement for Rev.:00 | 2 / 4 | 20.07.2007 |