Alarm Conditions

 

 

Condition

Alarm

 

 

Battery Mode (utility failure)

One short beep every 10 seconds; more than 2 minutes

of run time remaining

 

Low Battery

Two short beeps every 5 seconds; less than 2 minutes

of run time remaining

 

Output Overload (bypass)

One short beep every half second

 

 

Overtemperature (bypass)

A one-second beep every 4 seconds

 

 

DC Bus Overvoltage (bypass)

A one-second beep every 4 seconds

 

 

Control Power Supply

A one-second beep every 4 seconds

Failure (bypass)

 

PFC Failure (bypass)

A one-second beep every 4 seconds

 

 

Inverter Failure

A one-second beep every 4 seconds

 

 

Battery Test Failure

A 2-second beep every minute

 

 