Installation
2.0INSTALLATION
2.1Preliminary checks
Before beginning to install the RMP, verify that the equipment has reached site in its own packaging and in good general condition. Please notify immediately the shipper, Emerson Network Power and your local Liebert representative of any damage.
These items should be included in the package:
•RMP box with LCD screen
•4 mounting screws
•4 plastic wall anchors
•2 Phoenix connectors for connection with the UPS.
•User manual
2.2Location
The RMP is designed for indoor use and should be installed in an environment with clean air and ade- quate ventilation to keep the temperature within the specified operating range (see Table 17).
If the RMP is to be installed on a wall or other vertical surface, ensure that the surface can bear the weight (see Table 16) and there is no water leakage.
2.3Power Supply
The RMP requires a 120V/230V AC input (for detailed electrical specifications, see Table 18).
Figure 3 RMP electrical input plug
15.6mm
14mm ![](/images/new-backgrounds/1196321/19632115xi3.webp)
2.4Cable Specifications
4mm
Connect the RMP to the Liebert NX with a
Table 2 | Communication cable specifications | ||
|
|
|
|
No |
| Item | Specification |
|
|
| |
1 | Connector type | Both terminals are all | |
|
|
| |
2 | Cable Length | <100m | |
|
|
| |
3 | Cable type | a shielded and twisted pair of 0.5 to 1 mm2 | |
4 | Connection mode | See Figure 4 | |
|
|
|
|
4