Specifications

Power

 

24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W, 48VDC

Dimensions

 

Module: 11.3 x 0.56 x 7.5 (287 x 14.2 x 190.5)

 

W x D x H: in. (mm)

 

Enclosure (brushed aluminum): 14.25 x 2.85 x 12 (362 x 72.4 x 304.8)

Communication Ports

 

 

 

• Ethernet Port

 

10/100Base-T Fast Ethernet port.

 

• ARC156 Port

 

ARCNET156 or EIA-485 communication. In ARCNET156 mode, the port communicates via

 

BACnet ARC156.

 

 

 

 

 

 

• TPI Port S1

 

EIA-232/422/485 configurable port for interaction with 3rd-party building automation systems

 

via software-selectable protocols. May also be configured for remote modem access.

 

 

EIA-422/485

 

Each port can be individually set for different protocols & baud rates.

 

The number of ports varies by model:

 

Ports 1-12 - for

 

 

communication with

 

SiteLink-2E (SSW-2E)

SiteLink-4E (SSW-4E)

SiteLink-12E (SSW-12E)

equipment via

 

 

 

 

 

Ports 11-12

Ports 9-12

Ports 1-12

software-selectable

 

 

These two ports include

These four ports include

Four of these 12 ports (9-12)

protocols & baud

 

 

an option for EIA-232

an option for EIA-232

include an option for EIA-232

rates

 

 

connection.

connection.

connection.

 

 

Environmental

 

20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing

Operating Range

 

Note: Control modules should be installed within the building.

 

Memory

 

16 MByte non-volatile battery-backed SDRAM and 8 MByte Flash

Protection

 

Built-in surge and transient protection circuitry - internal solid state polyswitches on incoming

 

power and network communications connections

 

 

 

 

Battery

 

3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation

Fault Detection

 

Hardware watchdog timer

 

 

Agency Listings

 

UL, cUL, CE, FCC

 

 

Wiring Specifications

Connection

Supported Wire Types

Maximum Wire Length

Rating

 

 

 

 

Ethernet 10 BaseT

CAT 5

328 ft. (100m)

N/A

BACnet Port

MAGNUM Cable P/N A3-ARC-156-2

3000 ft. (915m)

N/A

Port S1 EIA-485

18-22 AWG Stranded & Shielded; 18 AWG (recommended)

1000 ft. (300m)

N/A

Non Plenum - Belden 9461; Plenum - Belden 88761

 

 

 

Port S1 EIA-232

18-22 AWG Stranded & Shielded; 18 AWG (recommended)

50 ft. (15m)

N/A

Non Plenum - Belden 9461; Plenum - Belden 88761

 

 

 

Ordering Information

Quantity

Part #

Description

 

 

 

 

SSW-12E

SiteLink-12E with enclosure - communicates with up to 12 Liebert unit controllers

 

SSW-12EWO

SiteLink-12E without enclosure - communicates with up to 12 Liebert unit controllers

 

SSW-4E

SiteLink-4E with enclosure - communicates with up to 4 Liebert unit controllers

 

SSW-4EWO

SiteLink-4E without enclosure - communicates with up to 4 Liebert unit controllers

 

SSW-2E

SiteLink-2E with enclosure - communicates with up to 2 Liebert unit controllers

 

SSW-2EWO

SiteLink-2E without enclosure - communicates with up to 2 Liebert unit controllers

 

 

 

Liebert Corporation

1050 Dearborn Drive

Telephone: 1-800-877-9222

P.O. Box 29186

Facsimile: 1-614-841-6022

Columbus, OH 43229

www.liebert.com

© 2007 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

SL-27218_REV0_01-07

4

Page 4
Image 4
Emerson SiteLink-12E, SiteLink-2E, SiteLink-4E dimensions Wiring Specifications, Ordering Information