Emerson SL-22075 INSTALLATION INSTRUCTIONS continued from page, Suggested Breaker And Wire Size

Models: SL-22075

1 12
Download 12 pages 159 b
Page 8
Image 8
INSTALLATION INSTRUCTIONS (continued from page 6)

Surge Protective Devices

INSTALLATION INSTRUCTIONS (continued from page 6)

4.Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical distribution system, keep all conductors as short as possible and avoid sharp bends.

5.Connection to the unit’s summary alarm contacts shall be with #18 – 22 AWG. The ratings of the Form ‘C’ contacts are

5amps at 250 VAC maximum with a power factor of 1.0. For additional information, see “Monitoring” section.

6.Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-721-8840.

7.Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-721-8840.

8.The protection modules in these SPDs may be replaceable, contact Liebert/Emerson Network Power Surge Protection for replacement.

If the SPD model is a Wye configured unit (4W+G), and a Neutral connection is not available, please contact factory.

SUGGESTED BREAKER AND WIRE SIZE

 

 

Allowable Range

 

Factory Suggested Size

Model #

Circuit Breaker Size

Connection Wire Size

Circuit Breaker

Connection

 

With Disconnect

Without Disconnect

With Disconnect

Without Disconnect

Size

Wire Size

SH025

15A – 150A

 

#8 – 1/O AWG

 

60 Amp

#6 AWG

SH032

15A – 175 A

15A – 175A

#8 – 1/O AWG

#14 – 2/O AWG

80 Amp

#4 AWG

SH040

15A – 175A

#8 – 1/O AWG

80 Amp

#4 AWG

 

 

SH075

15A – 175A

 

#8 – 1/O AWG

 

100 Amp

#2 AWG

Installation, Operation and Maintenance Manual

7

Liebert SPDs SL-22075 Rev 0, 9/2010

Page 8
Image 8