Emerson SL-31080 specifications Troubleshooting - Humidity Signal Verification, 4 to 20 mA Signal

Models: SL-31080

1 3
Download 3 pages 45.6 Kb
Page 3
Image 3
Troubleshooting - Humidity Signal Verification

Troubleshooting - Humidity Signal Verification

4 to 20 mA Signal

You will measure the humidity output by placing an ammeter in series with the controller input. The control- ler input is connected to the terminal marked “Ch1 or Ch2” on the humidity board.

1.Verify the unit is terminated properly using Figure 2 shown below, and set your meter to the “Volts” setting.

2.Verify you have 24 VDC supplied to the unit by measuring between the “V+” and “GND” terminals at the sensor, as shown below in Figure 1.

3.Set your meter to “Amps” and measure the output between “Ch1 or Ch2” and the controller input as shown below in Figure 1.

4.Use the following formula to determine what humidity the sensor is reading:

(mA - 4) / 0.16 = %RH

where mA is the current reading from the ammeter (in mA)

Example:

If the current reading is 16 mA, then: %RH = (16 - 4) / 0.16

=12 / 0.16

=75%

Figure 1 Supply Voltage and 4-20mA Verification

Figure 2 4 to 20 mA Output Connection

GND(-)

POWER SUPPLY

V+

+ A -

+

V

-

GND(-)

CONTROLLER

Analog Input

GND(-)

POWER SUPPLY

V+

GND(-)

CONTROLLER

Analog Input

V+ Ch1 or

Ch2

ROOM SENSOR

V+ Ch1 or

Ch2

ROOM SENSOR

SL-31080 Product Specification/Installation Sheet

page 3

6/03 (Rev. 0)

Page 3
Image 3
Emerson SL-31080 Troubleshooting - Humidity Signal Verification, 4 to 20 mA Signal, Supply Voltage and 4-20mAVerification