Rating Label
Each AutomaticClosed–Transition TransferSwitch contains
a rating label to define the loads and fault circuit withstand/
closing ratings.Refer to the label on the TransferSwitch for
specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipmentdamage.
!
Nameplate
The Transfer Switch nameplate includes data for each
specific 7000 Series ACTS. Use the switch only within the
limits shownon this nameplate. A typical Catalog Number
is shown on the next page with its elements explained.
Catalog Number Identification
Typical7000 Series ACTS catalog no. for switched neutral,
3 pole, 800 amp, 480 V,ATS in Type1 e nclosure:
H7ACTS B 3 800 N 5 C
Phase Poles
Neutral
A–solid
Amperes Volta ge Controller Enclosure
B–switched 5X –if
accessories
ordered
5–standard
G–type4*
C–type1
F–type3R
L–type12 *
3–thre
2–singl
D220
C208
E230
K415
M460
J400
L440
N480
G277
F240
H380 Q575
P550
R600
1200
1000
800
blank– none
blank– open type
600
* available600–1000 amp. sizes only
Tran sf er
Switch
power
connections
Group 5
Controller
Tran sf er
Control
&lights
800–1000 amp. sizes in typical enclosur e with location of customer connections
power
connections
field connections
terminal block TB
ground lug