4

© 2005 Liebert Corporation

All rights reserved throughout the world. Specifications subject

to change without notice.

® Liebert and the Liebert logo are registered trademarks of

Liebert Corporation. All names referred to are trademarks or

registered trademarks of their respective owners.

SL-31061 (2/05) Rev.1

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, OH 43229

Telephone: 1-800-877-9222

Facsimile: 1-614-841-6022

www.liebert.com

SpecificationsOrdering Information
Small Enclosure Large Enclosure I/O Expansion Module
UMS02400 115VAC
UML11500
230VAC
UML23000 UMEXP
Input Power
Requirements
24VAC±10% of
nominal; 50/60 Hz,
1.3A, 30VA
115VAC±10% of
nominal; 60Hz,
4A, 460VA
230VAC±10% of
nominal; 50Hz,
0.5A, 115VA
24VAC±10% of
nominal; 50/60 Hz,
0.6A, 15VA, Class 2
Dimensions
W x D x H, in. (mm)
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
18 x 2-3/4 x 18
(457.2 x 69.85 x 457.2)
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
Weight (Assembled) 7.68 lb. (3.48 kg) 20.56 lb. (9.33 kg) 7.68 lb. (3.48 kg)
Enclosure Type NEMA 1 NEMA 1
Liquid Crystal Display Four line, 20 character, backlit
Mounting Surface Building Wall or Structural Member
Ambient Operating
Environment
32°F to 104°F (0°C to 40°C)
0% RH to 95% RH (non-condensing)
Modem/Clock Specifics
Modem Type Embedded 14.4K bps
Clock Type Real-Time Clock
Clock battery backup type Lithium Cell (non-replaceable)
Clock battery life 7 years, constant, no power
Modem battery backup type Nickel Cadmium (replaceable)
Modem battery life 10 minutes at full load
Communications
Local EIA232 —
Remote: Modem Baud rate 9600 bps; Parity=None; Data bits=8; Stop bits=1
Remote: Supported pagers 9600 E-7-1 supports TAPI protocol version 1.8
SiteScan Web IGM Protocol, EIA422
Expansion Board (optional) EIA485 EIA485
Agency Listings
UL UL3121 UL1012 UL1585
CSA C22.2 No. 1010 C22.2 No. 66 and C22.2 No. 107.1
CE Yes Yes —
FCC Compliance CFR 47 Part 15 N/A
Inputs & Outputs (Quantity)
Digital Inputs Dry Contact Closure
24VDC, 10 mA (8)
Dry Contact Closure
24VDC, 10 mA (16)
Analog Inputs 4-20mA signal input with selectable power source of 12VDC or 24VDC (4)
Digital Outputs 24VAC, 3A (8) 240VAC, 2A (8)
Common Alarm Outputs 24VAC, 3A (2)
Quantity Product # Description
UMS02400 Universal Monitor small enclosure
UML11500 Universal Monitor large enclosure with 115VAC Transformer Module
UML23000 Universal Monitor large enclosure with 230VAC Transformer Module
TM115 Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle
TM230 Transformer Module 230VAC with two 24VAC outputs (40VA each)
UMEXP I/O Expansion Module