Customer Wiring
Input power (input to TB3)
Pin 1(+)
Pin
Modbus output for BMS (output from TB2)
TB1: Pin 1 (+), Pin 2
TB2: Pin 1 (+), Pin 2
Network port
for NMS and
Web access
DTE serial port for configuration (requires
IGMnet or Liebert SiteScan® Comms from unit (input to TB1 or P1)
Refer to user manual for details
Specifications
Power | AC Inputs | 18 - 24 VAC; 50/60 Hz | |
DC Inputs | 12 - 36VDC | ||
Requirements | |||
|
| ||
Power Consumption | 6VA maximum | ||
| |||
|
|
| |
Dimensions - W x D x H: in. (mm) | 7 x 4 x 1.5 (178 x 102 x 38) | ||
Weight | Net - oz. (kg) | 7 (0.2) | |
|
| ||
Shipping - lb. (kg) | 1.3 (0.6) | ||
| |||
|
|
| |
Ambient Operating Environment, °F (°C) | 32 to 104 (0 to 40); 10% to 90% RH | ||
Ambient Storage Temperature, °F (°C) | |||
Protection |
| SELV Isolated User Connections, Watchdog Timer Circuitry | |
| Service Terminal | DB9F, DTE | |
Communication | Unit Input | TB1, | |
Communications | P1, | ||
Ports |
|
| |
Modbus | TB2, | ||
| |||
|
|
| |
| Ethernet Communications | RJ45 | |
|
|
|
Wiring Specifications
Connection | Supported Wire Types | Maximum Wire Length | |
|
|
| |
TB1 | 1000 ft. (300m) | ||
Non Plenum - Belden 9461; Plenum - Belden 88761 | |||
|
| ||
TB2 | 3000 ft. (915m) | ||
Non Plenum - Belden 9461; Plenum - Belden 88761 | |||
|
| ||
TB3 (Power Input) | 20 ft. (6m) | ||
Non Plenum - Belden 8770; Plenum - Belden 88770 | |||
|
| ||
DB9F Connector | DTE Null Modem Cable | 50 ft. (15m) | |
|
|
| |
RJ45 Connector | Standard Category 5 Cable | 328 ft. (100m) | |
|
|
|
Liebert Corporation
1050 Dearborn Drive | Telephone: |
P.O. Box 29186 | Facsimile: |
Columbus, OH 43229 | www.liebert.com |
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.