emi ENGINEERING Submittal UNH-T2H-T3H-T4H
Manufacturer reserves the right to change these specifications at any time without incurring obligation.
Electrical Specifications Continued
Outdoor | Power Supply | Control* | Compressor | Outdoor Fan Motor | Unit |
|
| |||||||
|
| MCA | MOCP | |||||||||||
Unit |
|
|
|
|
|
|
|
| FLA | |||||
Volts | Min | Max | Qty | RLA | LRA | Qty | FLA | Hp |
|
| ||||
|
|
|
|
| ||||||||||
T3H2240 | 208/230 | 197 | 240 | 24 | 2 | 4.3 | 27.0 | 1 | 1.8 | 0.33 | 19.2 | 21.4 | 30 | |
1 | 8.8 | 54.0 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
T3H2220 | 208/230 | 197 | 240 | 24 | 3 | 4.3 | 27.0 | 1 | 1.8 | 0.33 | 14.7 | 15.8 | 20 | |
T4H9999 | 208/230 | 197 | 240 | 24 | 4 | 3.4 | 23.0 | 1 | 1.8 | 0.33 | 15.4 | 16.3 | 20 | |
T4H9992 | 208/230 | 197 | 240 | 24 | 3 | 3.4 | 23.0 | 1 | 1.8 | 0.33 | 16.3 | 17.4 | 20 | |
1 | 4.3 | 27.0 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
T4H9922 | 208/230 | 197 | 240 | 24 | 2 | 3.4 | 23.0 | 1 | 1.8 | 0.33 | 17.2 | 18.3 | 20 | |
2 | 4.3 | 27.0 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
T4H9222 | 208/230 | 197 | 240 | 24 | 1 | 3.4 | 23.0 | 1 | 1.8 | 0.33 | 18.1 | 19.2 | 20 | |
3 | 4.3 | 27.0 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
T4H2222 | 208/230 | 197 | 240 | 24 | 4 | 4.3 | 27.0 | 1 | 1.8 | 0.33 | 19.0 | 20.1 | 25 |
Note: * - Control Voltage is supplied from the indoor unit. No separate supply required.
Sound Data
Unit | Sound dBA |
UNH09 or UNH12 | 51 |
UNH24 | 56 |
T2H | 70 |
T3H | 70 |
T4H | 70 |
Note: Sound data for indoor unit at high speed, 230 V Sound data for outdoor unit at 230V
Weight Data
Unit | Weight, lbs (kg) | |
UNH09 | 92 | (41.8) |
UNH12 | 95 | (43.2) |
UNH24 | 116 (52.7) | |
T2H | 325 | (147.7) |
T3H | 325 | (147.7) |
T4H | 325 | (147.7) |
Interconnecting Tubing Specifications
Indoor | Outdoor | Maximum Separation, | Maximum Elevation | Liquid | Suction | Condensate | |
Circuit | Difference | ||||||
Unit | Equivalent ft (m) | Line OD | Line OD | Line ID | |||
capacity | ft (m) | ||||||
|
|
|
|
| |||
UNH09 | 9,000 Btuh | 100 (30.5) | 35 (10.7) | 1/4” | 1/2” | 1/2” | |
|
|
|
|
|
|
| |
UNH12 | 12,000 Btuh | 100 (30.5) | 35 (10.7) | 1/4” | 1/2” | 1/2” | |
|
|
|
|
|
|
| |
UNH24 | 18,000 Btuh | 100 (30.5) | 35 (10.7) | 3/8” | 5/8”* | 1/2” | |
UNH24 | 24,000 Btuh | 100 (30.5) | 35 (10.7) | 3/8” | 3/4” | 1/2” |
* UNH24 Suction Connection size is 3/4” O.D. and must bush down at the UNH Unit.
INDOOR AIR FLOW
Indoor Unit | CFM (l/s) | ||
High Speed | Low Speed | ||
| |||
UNH09 | 425 (200) | 375 (175) | |
or | |||
UNH12 |
|
| |
|
|
| |
UNH24 | 700 (350) | 550 (250) | |
|
|
|
Coil | ft/min (m/s) | Air Throw, ft. (m) |
Dry | 900 (4.6) | 15 (4.6) |
|
| |
|
|
|
| 1,225 (6.2) | 24 (7.3) |
|
|
|
Enviromaster International LLC | 5 | Rome, New York, USA |