Enerco HSU 75 Electrical Connections, Figure Gas Supply Connection, Line Voltage Field Wiring

Models: HSU 45 HSU 75

1 36
Download 36 pages 62.75 Kb
Page 10
Image 10
LINE VOLTAGE FIELD WIRING

 

LINE VOLTAGE FIELD WIRING

 

UNIT

L1

BLACK

 

BLACK

N

WHITE

 

 

WHITE

EQUIPMENT

GROUND

BLACK WIRE WITH WHITE TAPE OR

WHITE WIRE WITHOUT TAPE

FIGURE 7

GAS SUPPLY CONNECTION

 

MANUAL

 

MAIN SHUT-OFF VALVE

 

(FURNISHED BY INSTALLER)

GROUNDED

 

JOINT UNION

 

1/8 NPT

GAS FLOW

PLUGGED TAP

 

DRIP LEG

 

FIGURE 8

GAS SUPPLY TO UNIT HEATER

MANUAL MAIN SHUT-OFF VALVE

WILL NOT HOLD NORMAL TEST

PRESSUREISOLATE GAS VALVE

CAP

UNIT HEATER

FIGURE 9

5.Test for spillage at the draft hood relief opening after five minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.

7.If improper venting is observed during any of the above tests, the common venting system must be corrected. The common venting system should be resized to approach the minimum size as determined by using the appropriate tables in Appendix G in the current standards of the National Fuel

Gas Code, ANSI Z223-1 in the U.S.A. and the appropriate

Category I Natural Gas and Propane appliances venting sizing tables in the current standards of the CSA B149.1 Natural Gas and Propane Installation Code in Canada.

NOTE Local codes may supersede any of the above provisions.

ELECTRICAL CONNECTIONS

NOTE The MHU/HSU series unit heaters use a direct spark ignition system. There is no pilot necessary as the spark lights the main burner as the gas valve is turned on. The direct spark

FIGURE 7 WARNING

Electric shock hazard. Can cause injury or death. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water.

FIGURE 8 WARNING

Danger of explosion. Can cause injury or product or property damage. If over- heating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.

ELECTRICAL CONNECTIONS WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

Manual background WARNING

Danger of explosion and fire. Can cause injury or product or property damage. You must follow these instructions exactly.

Enerco Compact Unit Heater

10

Operating Instructions and Owner’s Manual

Page 10
Image 10
Enerco HSU 75, HSU 45 Electrical Connections, Figure Gas Supply Connection, Figure Gas Supply To Unit Heater