2151
SYSTEM SENSOR
LOW PROFILE, PHOTOELECTRONIC,
DESCRIPTION
The System Sensor 2151 low profile photoelectronic smoke detector is specifically designed to meet the perfor- mance requirements of fire detection/alarm systems. The 2151 detector uses a
The 2151 detector is of
Two visible LEDs on each detector flash every ten seconds indicating that power is being applied to the detector. The LEDs light steadily when the detector is in alarm. A remote LED annunciator is available as an optional accessory.
The 2151 is UL Listed for mounting inside ducts up to a ve- locity of 3,000 FPM.
Functional testing is performed by placing a test magnet against the cover. The LED on the detector should light within 30 seconds.
Field metering of detector sensitivity may be performed with the aid of a voltmeter and Test Kit, Part No. MOD 400R.
APPROVALS
FEATURES
•Low Profile Construction
•Easy
•
•Test Switch
•360o View Angle of Alarm LEDs
•Compatible with FCI Control Panels
•Audible Sounder Base (Optional)
•Field Metering of Detector Sensitivity
•Removable Insect Screen and Cover for Field Cleaning
•
| TECHNICAL SPECIFICATIONS |
Sensitivity | 3.0 %/ft. (nominal) |
Operating voltage | 8.5 - 35 VDC (24 VDC nominal) |
Standby current | 120 uA maximum |
Operating temperature | 32o to 120o F (0o to 49o C) |
Operating humidity | 10 % - 93 % relative humidity |
Air velocity | 3,000 feet per minute maximum |
Construction | |
Diameter | 6.2 inches (15.5 cm) (flanged base) |
Height | 1.7 inches (4.2 cm) |
Weight | 3.6 oz. (104 g) |
16 Southwest Park, Westwood, MA 02090 USA TEL: (781)
An ISO 9001 Certified Company | |
|