FCI Home Appliances 12-64B manual Operation, Wiring the Instrument into the Customer’s Application

Models: 12-64B 8-66B

1 4
Download 4 pages 40.49 Kb
Page 3
Image 3
Wiring the Instrument into the Customer’s Application:

INSTALLATION, OPERATION AND TROUBLESHOOTING GUIDE

FLUID COMPONENTS INTL

Wiring the Instrument into the Customer’s Application:

FCI recommends routing conduit to the enclosure. Below is a table to determine the wire size needed to route to the instrument. Connect the customer’s application (relays, lights, etc,.) to the terminal block switch points as required. The input power is either 115 VAC, 230 VAC or 24 VDC and was specified when the instrument was purchased. Check the part number or paperwork received with the instrument to determine the type of power to be applied to the instrument. Connect the power as shown.

 

Maxim um D is tance for AWG

 

 

C onnection

10 ft.

50 ft.

100 ft.

250 ft.

500 ft.

1000 ft.

 

(3 m )

(15 m )

(31 m )

(76 m )

(152 m )

(305 m )

Pow er

22

22

22

20

18

16

R elay

24

22

20

16

12

N /A

Step 5. Operation

12-64 Alarm Set Point Procedure:

Wiring Diagram

 

1.Set the flow at the desired rate.

2.Apply power to the instrument and allow 10 minutes for the sensing element to become active and stabilize.

3.Locate the potentiometer (R5) and the red LED on the control circuit. (See the picture below:)

4.Choose procedure A or B below.

A. Detecting No Flow or Decreasing Flow Rate

If the LED is off, turn the potentiometer clockwise until the LED turns on. If the LED is on, turn the potentiometer counterclockwise until the LED turns off, then turn the potentiometer clockwise until the LED just turns on. With the LED on, turn the potentiometer slowly counterclockwise until the LED just turns off. Turn the potentiometer one-half turn past the point at which the LED just turns off. Be aware that the potentiometer may have up to one quarter turn of hysteresis. If the mark is overshot, the procedure should be repeated. (See the picture and diagram below:)

B. Detecting Maximum Flow or Increasing Flow Rate

If the LED is on, turn the potentiometer counterclockwise until the LED turns off. If the LED is off, turn the potentiometer clockwise until the LED turns on, then turn the potentiometer counter clockwise until the LED just turns off. With the LED off, turn the potentiometer slowly, clockwise until the LED just turns on. Turn the potentiometer one-half turn past the point at which the LED just turns on. Be aware that the potentiometer may have up to one quarter turn of hysteresis. If the mark is overshot, the procedure should be repeated. (See the picture and diagram below:)

Jumper on J12.

J12, J13 Relay de-energized at no flow / dry.

Jumper on J13. Relay de-energized at flow / wet.

R5, set point potentiometer.

Set point LED.

12-64/866 Plug and Switch Orientation

Setting Alarm Switch Point

5.Test switch operation by increasing or decreasing the flow to activate the alarm.

Doc. No. 06EN003322 Rev. -

3

Model 12-64/8-66

Page 3
Image 3
FCI Home Appliances 12-64B Operation, Wiring the Instrument into the Customer’s Application, Alarm Set Point Procedure