C10 High Efficiency Series
MODEL SPECIFICATIONS
MODEL NUMBER
PERFORMANCE DATA
C1018BBD1VF C1024BBD1VF C1030BBD1VF
C1036BBD1VF
C1036BBD3VF
C1036BBD4VF
NOMINAL COOLING BTU/H |
| 18 000 | 22 400 | 28 600 |
| 34 000 |
|
SEER |
| 10.0 | 10.0 | 10.0 |
| 10.0 |
|
CFM |
| 600 | 800 | 1000 |
| 1200 |
|
VOLTS/HZ/PHASE |
| 460/60/3 | |||||
VOLTAGE RANGE |
| ||||||
OPERATING CURRENT AMPS | ➀ | 9.8 | 10.8 | 11.4 | 17.0 | 12.7 | 5.9 |
MIN. WIRE AMPACITY |
| 13.0 | 14.5 | 20.0 | 21.7 | 16.0 | 15.0 |
MAX. HACR BREAKER | ➁ | 20 | 20 | 30 | 30 | 25 | 15 |
COMPRESSOR DATA
RLA
LRA
FAN DATA
8.8 | 9.8 | 11.4 | 15.2 | 10.9 | 4.7 |
49 | 60 | 75 | 96 | 70 | 33 |
DIAMETER | 18 INCH / 3 BLADE | 18 INCH / 3 BLADE | 18 INCH / 3 BLADE | 18 INCH / 3 BLADE | ||
MOTOR TYPE | PSC | PSC | PSC | PSC | ||
HP (W) / FLA | 1/6 / 1.0 | 1/6 / 1.0 | 1/6 / 1.0 | 1/6 / 1.0 |
| 1/4 / 1.2 |
RPM | 1075 | 1075 | 1075 | 1075 |
| |
CFM | 1800 | 1800 | 1800 | 1800 |
| |
OUTDOOR COIL |
|
|
|
|
|
|
TYPE |
| ENHANCED ALUMINUM PLATE FIN / RIFLED COPPER TUBE | ||||
FACE AREA | 8.0 | 8.0 | 8.0 |
| 9.8 |
|
O.D. / | 5/16 / | 5/16 / | 3/8 / | 3/8 | / |
|
REFRIGERANT LINE CONNECTIONS (SERVICE VALVE PORT I.D.)
LIQUID
VAPOR
WEIGHTS
3/8 ID | 3/8 ID | 3/8 ID | 3/8 ID |
3/4 ID | 3/4 ID | 3/4 ID | 3/4 ID |
|
|
|
|
NET WEIGHT — lbs. | 119 | 119 | 128 | 139 |
SHIPPING WEIGHT — lbs. | 125 | 125 | 134 | 146 |
COOLING PERFORMANCE DATA MATCHING EVAPORATOR COIL
OUTDOOR | EVAPORATOR | RATINGS AT STANDARD CONDITIONS |
| COOLING DATA AT EXTENDED OUTDOOR AMBIENTS °F.M.B.T.U.H. |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||
UNIT | COIL➂ | BTUH |
| CFM |
| 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | |
MODEL* | SEER |
| ||||||||||||
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
C1018BBD | E3009A | 18 000 | 10 | 600 | TOTAL | 20 200 | 19 700 | 19 100 | 18 000 | 17 600 | 16 800 | 15 900 | 15 000 | |
SENSIBLE | 14 500 | 14 200 | 13 750 | 13 000 | 12 700 | 12 100 | 11 400 | 10 800 | ||||||
|
|
|
|
| ||||||||||
C1024BBD | E3009A | 22 400 | 10 | 800 | TOTAL | 25 500 | 24 700 | 23 800 | 22 400 | 22 200 | 21 500 | 20 700 | 19 900 | |
SENSIBLE | 18 300 | 17 800 | 17 100 | 16 100 | 15 900 | 15 500 | 14 900 | 14 330 | ||||||
|
|
|
|
| ||||||||||
C1030BBD | E3618A | 28 600 | 10 | 1000 | TOTAL | 31 300 | 30 500 | 29 800 | 28 600 | 28 000 | 27 000 | 26 000 | 25 000 | |
SENSIBLE | 22 500 | 22 000 | 21 500 | 19 300 | 20 200 | 19 400 | 18 700 | 18 000 | ||||||
|
|
|
|
| ||||||||||
C1036BBD | E3618A | 34 000 | 10 | 1200 | TOTAL | 36 400 | 36 000 | 35 500 | 34 000 | 32 400 | 30 700 | 29 100 | 27 500 | |
SENSIBLE | 26 200 | 25 900 | 25 600 | 24 500 | 23 300 | 22 100 | 20 900 | 19 800 | ||||||
|
|
|
|
| ||||||||||
C1042BBD | E4824A | 40 000 | 10 | 1300 | TOTAL | 43 000 | 42 000 | 41 000 | 40 000 | 38 500 | 37 000 | 35 500 | 34 000 | |
SENSIBLE | 31 000 | 30 200 | 29 500 | 28 800 | 27 700 | 26 600 | 25 560 | 24 500 | ||||||
|
|
|
|
| ||||||||||
C1048BBD | E6026A | 45000 | 10 | 1600 | TOTAL | 49 700 | 48 500 | 47 300 | 46 000 | 44 400 | 43 000 | 41 500 | 39 800 | |
SENSIBLE | 35 800 | 34 900 | 34 000 | 33 100 | 32 000 | 31 000 | 29 900 | 28 600 | ||||||
|
|
|
|
| ||||||||||
C1060CBD | E6037A | 56 000 | 10 | 1750 | TOTAL | 58 800 | 57 900 | 56 900 | 56 000 | 54 000 | 52 000 | 50 000 | 48 000 | |
SENSIBLE | 42 300 | 41 700 | 41 000 | 40 300 | 38 900 | 37 400 | 36 000 | 34 600 | ||||||
|
|
|
|
|
*Basic model number only. See unit nomenclature on the last page for exact model number.
FOOTNOTES:
➀Amps at 104˚F OD temp. 80˚F DB / 67˚F WB indoor temp. ➁ Time delay type fuse for HACR Circuit Breaker. ➂ For indoor coils nomenclature see indoor coil specification sheet. ➃ Air Handler includes Evaporator Coil.