GAS SPILLAGE SENSING KIT

Model: GSK-3, GSK-4, GSK-250M

Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft hoods, draft diverter, or gas barometric draft controls. This device is installed to detect flue gas spillage caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.

Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.

CAUTION: Disconnect Electrical Power When Wiring Spillage Switch

 

MODEL

 

 

P/N

 

 

CONTACT

 

 

LOAD RATING

 

 

SETPOINT °F

 

 

RESET

 

 

SWITCH

 

 

APPLICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MATERIAL

 

 

AMPS

 

 

VOLTS

 

 

 

 

 

 

TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GSK-3

 

46086400

 

 

GOLD

 

24VA

 

 

mV-24AC

 

180

 

 

MANUAL

 

 

SPST NC

 

 

Gas-fired mV or 24VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas-fired mV or 24VAC,

 

GSK-4

 

46086402

 

 

GOLD

 

24VA

 

 

mV-24AC

 

200

 

 

MANUAL

 

 

SPST NC

 

 

where slower response

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time is a requirement

 

GSK-250M

 

46086404

 

 

SILVER

 

24VA

 

 

mV-24AC

 

250

 

 

MANUAL

 

 

SPST NC

 

 

Steam Boilers

Page 1
Image 1
Field Controls GSK-3, GSK-4, GSK-250M installation instructions GAS Spillage Sensing KIT, Type