VII. TROUBLESHOOTING GUIDE

5.Remove lamp carefully, by sliding the lamp to the left through the hole on the left side of the chamber. After exposing the connection end of the lamp inside the chamber, remove the lamp through the front of the unit.

NOTE: When replacing the lamp, always wipe off lamp with the supplied alcohol wipe after installing.

6.Replace the lamp by first guiding the end of the lamp through the hole on the left side of the UV chamber. Next, guide the other end of the lamp through the hole on the right side of the UV chamber. Hold the lamp in position while rotating the swivel bracket into position. Secure the lamp into position by tightening the wing nut onto the swivel bracket.

NOTE: UV lamps contain a small amount of mercury, like a typical fluorescent lamp. Check with your local waste management authority for local disposal or recycling requirements. According to the EPA’s Universal Waste Rule, these types of lamps may be disposed of into household waste.

7. Close the Chamber access door and rotate the door clips to secure the door into position.

WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.

8.Plug the power cord back into the wall receptacle or restore power to the UV- 1500C circuit.

9.Turn the knob on the speed control to the on position, press the door switch in, and allow the motor to start and the lamp to light. Wait 30 seconds.

10.Reset the lamp timer by using the eraser end of a pencil or the blunt end of a plastic ink pen and press and hold the timer-reset button on the circuit board for 30-45 seconds (See Figure 21). After releasing the timer-reset button the LED on the front of the unit will flash twice indicating the timing circuit has been reset.

11.Release the door switch, turn the knob on the speed control to the off position and close the front cover of the unit. Secure the cover with the door mounting screws.

12.Turn the speed control knob clockwise to turn on the unit and adjust the motor/fan speed control to the desired airflow. After the fan has started the LED light will show a continuous “GREEN” color indicating proper unit operation

Reset

Button

Figure 21

REPLACING AIR FILTERS

1.Loosen the two door-mounting screws on front cover of the UV-1500C. Open the cover to expose the filters and the air purification chamber. (See Figure 17)

2.Replace the 12” by 12” air filter by removing the filter and replacing the filter with the wire support side of the filter installed toward the fan intake of the unit. (See Figure 18)

3.Replace the carbon filter by removing the old filter and inserting the new filter back into the filter holder being sure safety switch is depressed.

VII. TROUBLESHOOTING GUIDE

1.If the LED is illuminating a “YELLOW” color and the circuit board alarm beeps every 15 minutes, then the lamp should be replaced soon.

2.If the LED is illuminating a “RED” color and the circuit board alarm beeps every 5 minutes, then the lamp should be replaced.

3.If lamp does not light up 1) be sure the safety switch located in the carbon filter chamber is depressed with pressure from the filter or 2) replace lamp.

4.If lamp still does not light up after checking the safety switch or replacing the lamp, replace ballast.

VIII. REPLACEMENT PARTS LIST

 

LAMP

 

 

BALLAST

 

YEARLY FILTER AND

 

 

 

 

LAMP REPLACEMENT KIT

 

 

 

 

 

 

 

(Field Controls Part Number)

 

(Field Controls Part Number)

(Field Controls Part Number)

46365401

 

46365514

 

46453600

 

 

 

 

 

 

 

For replacement parts, contact your local heating service company. Any questions, please contact Field Controls at:

Phone: 252-522-3031 Fax: 252-522-0214 Email: sales@fieldcontrols.com

WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Never operate the UV-Aire™ Air Purifying System with the UV chamber door open. Avoid touching the glass portion of the

lamp with your hands.