FS-8700-101_Setra Model 370 Digital Pressure Gage ManualPage 17 of 23

Appendix A. Advanced Topics

Appendix A.1. How Data Gets Stored

Appendix A.1.1. Pressure Data

Offset (where x is the offset

 

Notes

specified in the MD)

 

 

X + 0

 

Gage Pressure. A signed real number.

 

 

Gage Pressure Units. A whole number which is used

X + 1

 

as a lookup into the table provide in section

 

 

“Appendix A.2 Gage Pressure Units”

 

 

Gage Pressure Indicating Letter

X + 2

 

‘A’ = 65

 

‘G’ = 71

 

 

 

 

‘T’ = 84

X + 3

 

Set to 1 If the pressure reading reports the status as

 

‘OK’

 

 

X + 4

 

Set to 1 If the pressure reading reports the pressure

 

as a ‘SEA LEVEL’ reading

 

 

Appendix A.1.2. Status Data

If any fields are absent in the response to a poll for status data then the values are set to zero for that field.

 

Offset (where x is the offset

 

Notes

 

 

 

 

 

 

specified in the MD)

 

 

 

 

 

 

 

 

X + 0

 

‘ELEV:’ measurement. A signed real number.

 

 

X + 1

 

‘ELEV:’

engineering

units

index.

See

table

 

 

“Appendix A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

X + 2

 

‘MAX:’ measurement. A signed real number.

 

 

X + 3

 

‘MAX:’ engineering units index. See table “Appendix

 

 

A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

 

 

X + 4

 

‘MIN:’ measurement. A signed real number.

 

 

X + 5

 

‘MIN:’ engineering units index. See table “Appendix

 

 

A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

 

 

X + 6

 

‘HI ALARM:’ measurement. A signed real number.

 

X + 7

 

‘HI ALARM:’ engineering units index. See

table

 

 

“Appendix A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

X + 8

 

‘LO ALARM:’ measurement. A signed real number.

 

X + 9

 

‘LO ALARM:’ engineering units index. See

table

 

 

“Appendix A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

X + 10

‘ZERO:’ measurement. A signed real number.

 

 

X + 11

 

‘ZERO:’

engineering

units

index.

See

table

 

 

“Appendix A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

X + 12

 

‘UNIT:’ measurement. A signed real number.

 

 

X + 13

 

‘UNIT:’ engineering units index. See table “Appendix

 

 

A.2 Gage Pressure Units”

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 17
Image 17
FieldServer FS-8700-101 instruction manual Appendix A.1.2. Status Data, Offset where x is the offset Specified in the MD