4.Configuring the FieldServer as a SDD16 Client

For a detailed discussion on FieldServer configuration, please refer to the configuration manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a SDD16 Server.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for SDD16 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1.Data Arrays

 

Section Title

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

Column Title

Function

 

Legal Values

 

 

Data_Array_Name

Provide name for Data Array

 

Up to 15

alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT,

BIT, UInt16,

 

 

Data_Format

Provide data format. Each data array

SInt16, Packed_Bit, Byte,

 

 

can only take on one format.

 

Packed_Byte,

 

 

 

 

 

 

 

 

 

Swapped_Byte

 

 

 

Number of Data Objects. Must be

 

 

 

 

Data_Array_Length

larger than the data storage

area

1-10,000

 

 

 

required for the data being placed in

 

 

 

 

 

 

 

 

 

this array.

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

//Data Arrays

 

 

 

 

 

 

//

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

 

Digitals_01,

Bit,

16

 

 

 