Driver Manual |
4.Configuring the FieldServer as a GE-SRTP Driver Client
For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for
Note that in the tables, * in dicates an optional parameter, with the bold legal value being the default.
4.1 Data Arrays
Section Title |
|
|
Data_Arrays |
|
|
Column Title | Function | Legal Values |
Data_Array_Name | Provide name for Data Array | Up to 15 alphanumeric |
|
| characters |
Data_Format | Provide data format. Each data array can only | FLOAT, BIT, UInt16, SInt16, |
| take on one format. | Packed_Bit, Byte, |
|
| Packed_Byte, Swapped_Byte |
Data_Array_Length | Number of Data Objects. Must be larger than | |
| the data storage area required for the data |
|
| being placed in this array. |
|
|
|
|
Example
//Data Arrays
Data_Arrays |
|
|
Data_Array_Name, | Data_Format, | Data_Array_Length |
DA_AI_01, | UInt16, | 200 |
DA_AO_01, | UInt16, | 200 |
DA_DI_01, | Byte, | 200 |
DA_DO_01, | Byte, | 200 |
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408)
Visit our website: www.fieldserver.com