Firex 591S manual The indicator/control assembly provides, Duct Smoke Detector Remote Accessories

Models: 592SC 591S

1 2
Download 2 pages 43.81 Kb
Page 1
Image 1
The professional choice in fire safety.

The professional choice in fire safety.

NEW ACCESSORIES

The NEW remote accessories are designed to be used with Firex duct smoke detectors to provide the most complete functionality ever available in such a device.

The remote accessory is available with either the single gang remote indicator/control (591 models), or with the addition of a single gang strobe assembly (592 models). Both versions are compatible with standard Decora style cover plates (choice of white, red or stainless steel). A strobe-only version (593 models) is available for retrofit upgrade of “controller only” installations.

The indicator/control assembly provides:

Visual indication of detector Pilot, Trouble and Alarm Functions

Selectable audible indication of Alarm, Trouble or both

Buzzer Silence function, with silenced indication and “ringback” following condition correction

Lamp/Buzzer test function

Key-Operated detector Test and Reset functions

Lever-operated “No-Tools” terminal block

Port for plugging in the optional strobe assembly

Black “DUCT SMOKE DETECTOR” decal included for front plate

Blue “SMOKE”, red “FIRE” strobe lens decals included for both horizontal and vertical mounting

Strobe Connection

The strobe assembly provides visual indication of alarm conditions, and is connected to the indicator/control assembly via the provided polarized connector.

To install the strobe module, simply plug the provided connector onto the pins as indicated on the rear of the indicator/control module. Snap the strobe lens into the cover plate, and install cover plate following completion of remote module wiring.

NOTE: The strobe and audible buzzer features are not ADA compliant, and not intended for life safety notification or evacuation purposes (public mode). These functions are for duct smoke detector status indication only (private mode).

Duct Smoke Detector Remote Accessories

Universal Voltage Models Compatible with230 VAC, 115 VAC, 24 VAC or 24 VDC operation

2650-760 Ionization • 2650-761 Photoelectric

2650-660 Ionization • 2650-661 Photoelectric
2650-560 Ionization • 2650-561 Photoelectric
591S

592SC

Audible Buzzer Configuration

There are two jumpers located on the rear of the indicator/control assembly. To enable audible buzzer operation for Alarm or Trouble conditions, simply leave the jumpers in place. To disable either or both functions, remove the appropriate jumper(s).

 

ALM

 

TBL

 

ALM

TBL

ALM

TBL

ALM

TBL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Buzzer will

Buzzer will

Buzzer will

Buzzer

function on

function on

function

will not

both Alarm

on Alarm

on Trouble

function

and Trouble

Condition

Condition

on Alarm

Conditions

 

only

only

or Trouble

 

 

 

 

 

 

 

 

 

 

 

Conditions

Page 1
Image 1
Firex 591S, 592SC manual The indicator/control assembly provides, Duct Smoke Detector Remote Accessories, New Accessories