•Install smoke alarms on peaked, cathedral, or gabled ceilings 3 feet from the highest point (measured horizontally). NFPA 72, Section
ACCEPTABLE IN
THIS AREA
PEAKED CEILING
•Install a smoke alarm in
attics which house electrical equipment like furnaces, air condi- tioners, or heaters.
DO NOT install smoke alarms:
Near appliances or areas where normal combustion regularly occurs (kitchens, near furnaces, hot water heaters). Use specialized smoke alarms with unwanted alarm control for these areas.
In areas with high humidity, like bathrooms or areas near dishwashers or washing machines. Install at least 10 feet (3 meters) away from these areas, if possible.
Near air returns or heating and cooling supply vents. Install at least 3 feet (0.9 meters) away from these areas. The air could blow smoke away from the detector, interrupting its alarm.
In rooms where temperatures may fall below 40°F (4°C) or rise above 100°F (38°C).
In extremely dusty, dirty, or
|
| HOW TO INSTALL |
|
| THIS SMOKE ALARM |
! | DANGER: | ELECTRICAL SHOCK HAZARD. Turn off |
|
| power at the main fuse box or circuit |
|
| breaker by removing the fuse or switching |
! |
| the circuit breaker to the OFF position. |
WARNING: | This smoke alarm should be installed only | |
|
| by a qualified electrician. Smoke alarm |
|
| installation must be in accordance with the |
|
| requirements of Article 760 of the National |
|
| Electrical Code and any local codes that |
|
| may apply. |
THIS SMOKE ALARM SHOULD BE INSTALLED IN ACCOR- DANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIA- TION’S STANDARD 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
•Install smoke alarm on a
1.From back of smoke alarm, remove mounting plate. (To later engage
2.Align recessed slots on plate with mounting holes of a 4- inch octagon or single gang junction box.
3.Gently pull household wires through center hole of plate.
4.Secure plate to junction box with mounting screws.
5.With a small wire connector, connect white wire from connec- tor plug to white household wire.
6.Connect black wire from connector plug to black household wire.
7.If interconnection is desired, connect yellow wire from con- nector to interconnect wire between smoke alarms. See sec- tion INTERCONNECTING SMOKE ALARMS.
NOTE: If this will be a
wire with electrical tape and tuck into | FPAD | |
junction box. | ||
Battery | ||
| ||
8. Attach connector plug to pins on back of |
| |
smoke alarm. Plug will only fit one way |
| |
and will snap into place. |
|
9. Gently tug connector to be sure it is | Battery Door |
attached securely. | Remove thin plastic |
4