PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure
16, page 15).
2. Open main gas valve located on or near
gas meter for natural gas or open pro-
pane/LP supply tank valve.
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff
valve to gas regulator (Manual-Controlled
Models) or to gas control valve (Remote-
Ready Models) (see Figures 17 or 18,
page 15). Apply noncorrosive leak de-
tection uid to all joints. Bubbles forming
show a leak.
5. Correct all leaks at once.
6. Light replace (see Operating Fireplace,
page 18). Check all other internal joints
for leaks.
7. Turn off replace (see To Turn Off Gas to
Appliance, page 20 for Manual-Controlled
Models or page 21 for Remote-Ready
Models).