Venting Installation
Continued
Secure to Collars with
Duct Tape or Screws
Air Inlet | ||
Location | ||
Must Allow | ||
For Bushes | ||
or Snow | ||
| Air Inlet | |
| Termination | |
Vented Crawl Space | Vent Hood | |
Required for | ||
(Check Local Codes | ||
Wall Installation | ||
Before Installing in a | ||
| ||
Vented Crawl Space) |
|
Figure 13 - Outside Air Kit Installation
Chimney Pipe
The FMI PRODUCTS, LLC chimney is a
Each section of pipe comes in lengths of 12", 18" 36" and 48". The actual lineal gain for each is measured after each section is fully connected. Lineal gain is the actual measurable length of a part after two or more parts are connected.
| LINEAL GAIN |
| |
PART NO. | DESCRIPTION | GAIN | |
(V)3612ST | 52 3/4" | ||
| Fireplace |
| |
Flue Pipe | 46 5/8" | ||
|
| ||
Flue Pipe | 34 5/8" | ||
Flue Pipe | 22 5/8" | ||
|
| ||
Flue Pipe | 16 5/8" | ||
Flue Pipe | 10 5/8" | ||
|
| ||
Chase Style | 1" to 12" | ||
Termination | |||
|
| ||
Round Top | 7" | ||
Termination | |||
|
|
Pipe Installation
The pipe sections must be assembled independently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked to- gether. When installing double wall
Figure 17, page 8).
WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed.Neveruseblowninsulation to fill the chimney enclosure.
15" Galvanized
Outer Pipe
12 3/8" | Hemmed |
Stainless | End |
Inner Pipe |
|
Figure 14 - Pipe Connection
Using ELBOW offsets and Supports
Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 15, page 8).
To achieve desired offset, you may install combinations of 12", 18", 36" and 48" length of double wall pipe (see offset chart and Figure 16, page 8).
The chimney support section is a 4" strap and 12" length of pipe. A chimney support is required every 30 feet above fireplace after a straight chimney run or above a return elbow after a straight chimney run (see Figure 17, page 8). This support is designed to relieve the extra weight load on fireplace and elbows
when high chimneys are installed.
www.fmiproducts.com | 7 |