1.3 LOCATIONS OF CONTROLS
| Operation |
| Off | : Turns air conditioner off. |
|
| Hi Fan | : High speed fan operation without | |
| Hi | Hi | ||
|
| cooling. | ||
| Off |
|
|
|
| Fan O | Cool | Lo Fan | : Low speed fan operation without |
|
|
| ||
Lo | O | Lo |
| cooling. |
Fan | Cool |
|
| |
|
|
| Hi Cool | : Cooling with high speed fan |
|
|
|
| operation. |
| Mode |
| Lo Cool | : Cooling with low speed fan |
|
|
| ||
|
|
|
| operation. |
Thermostat
This automatically controls the temperature of the indoor air.
Turn the knob clockwise for greater cooling. Point the arrow
for more moderate cooling.
WarmerCooler
Temperature
CAUTION : After switching the air conditioner from Cool to Off or Fan, wait at least 3 minutes before switching it back to Cool.
1.4 SAFETY PRECAUTIONS
1.When servicing, set the ROTARY SWITCH to Off and unplug the power cord.
2.Observe the original lead dress.
If a short circuit is found, replace all parts which have been overheated or damaged by the short cir- cuit.
3.After servicing, make an insulation resistance test to prevent the customer from being exposed to shock hazards.
1.5 INSULATION RESISTANCE TEST
1.Unplug the power cord and connect a jumper between 2 pins (black and white).
2.The grounding conductor (green or green and yel- low) is to be open.
3.Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all position [except Off] of the ROTARY SWITCH.
4.The value should be over 1 MΩ.