Frigidaire HV2736B PLANNING - continued, Specifications, Take Measurements, Plan The Ductwork

Models: HV2730B HV2736B

1 6
Download 6 pages 38.92 Kb
Page 2
Image 2
PLANNING - (continued)

PLANNING - (continued)

Note: The high level of air flow of this appliance may affect the gas flame on some types of gas cooktops. This is NORMAL and will cause no harm, but can be corrected by lowering the speed of the blower.

SPECIFICATIONS

VOLTS

AMPS

CFM

DUCT

120

4.0

500

3-1/4 X 10

TAKE MEASUREMENTS

1.Refer to the cooktop installation instructions for dimensions of cooktop, countertop cut-out, and cabinet requirements. The Model 2730 will fit in most 30" wide cabinets and the Model 2736 will fit in most 36" wide cabinets. However, it is recommended that oversized cabinets be used for easier installation.

2.Cooktop depth can vary greatly from one to another. This may cause the fit of these two appliances to be rather tight.

Pay special attention to the areas of potential interference highlighted above. A countertop with (A) a raised lip and/or (B) a backsplash may not allow enough flat countertop for a proper installation. Note that 2" of flat countertop is required behind cooktop and that 1-3/4" is necessary between the back edge of the cooktop and the inside of cabinet back.

PLAN THE DUCTWORK

RIGHT

DISCHARGE

LEFT

DISCHARGE

DOWN DISCHARGE (as shipped)

1.This downdraft blower system is designed for use with 3-1/4" x 10" ductwork (can be transitioned to 6" round). Three different discharge directions are available with side-to-side adjustment for accurate alignment of ductwork.

2.For best performance: Choose the ducting option which allows the shortest length of ductwork and a minimum number of elbows and transitions. Check location of floor joists, wall studs, electrical wiring or plumbing for possible interference. NOTE: The unit is shipped with the 3-1/4" x 10" discharge facing DOWN. See “CHANGING BLOWER DI- RECTION” on page 3, if necessary.

6" ROUND

3-1/4" X 10"

ELBOW

TO 6" RD.

 

TRANSITION

EQUALS 6 FT. OF

EQUALS 2

FT. OF

STRAIGHT DUCT

STRAIGHT DUCT

3-1/4" X 10"

90O ELBOW

EQUALS 8

FT. OF

STRAIGHT DUCT

3.The system will operate most efficiently when the ductwork does not exceed 40 feet of equivalent duct. The chart, above, shows equivalent feet of elbows and transitions. The number of feet of straight duct plus the equivalent feet of transitions and/or elbows to be used should equal 40 feet or less.

NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.

PLAN THE WIRING

1.The downdraft blower system draws 4 AMPS and requires a 120 VAC, 60 Hz circuit.

2.The unit has a 2 ft. long power cord with a 3-pronged plug. Plan to provide a grounded outlet in a location which will allow the unit’s power cord to reach. (Note: If the Model 2730 is being installed in a 30" wide cabinet or the Model 2736 is being installed in a 36" wide cabinet, the outlet cannot be located on the back wall of cabinet.) Outlet may also be wall-mounted, with access hole in cabinet.

2

Page 2
Image 2
Frigidaire HV2736B, HV2730B PLANNING - continued, Specifications, Take Measurements, Plan The Ductwork, Plan The Wiring