Remote Switching (Units with “R” Suffix Only*)
Model
In the most basic configuration, only two Class 1 wires and an SPST switch are needed to initiate an ON or OFF sequence. The switch may be either a momentary or
Maintained vs. Momentary Contact Switching
Maintained switches, such as most toggle switches and
Maintained switches are generally most convenient when there is only one remote location. When more than one switch location is required, momentary switches allow the sequence to be started from any location.
1.Disconnect the unit from AC power.
2.Remove the four screws that secure the top cover.
3.In the rear left corner of the circuit board, there is an area labeled “REMOTE CONTROL.” There are two pairs of terminals in this area, one labeled “MAINTAINED” and the other “MOMENTARY.” There is a small black jumper linking the MAINTAINED terminals. Slide it up and off, and replace itsecurely over the MOMENTARY terminals.
4.Reattach the top cover.
Maintained Mode
A simple connection of the REM IN terminal to the +12V terminal initiates an OFF sequence. Disconnecting it initiates an ON sequence. If the cable run is long, it is recommended that the REM IN wire be tied to the
The STATUS terminal is an output that may be used to illuminate an LED at the remote location to indicate that power is available at the PowerPort’s outlets. If it is high (+5V), the unit is ON (or at least in the process of sequencing ON); if low, the unit is OFF (or sequencing OFF). Simply connect the indicator LED between STATUS and ground (do not use a series resistor). If the LED does not light when the switch is in the ON position, check the polarity and reverse the LED leads (if it is wrong). If a Furman
In Maintained Mode, DO NOT USE the “START
Momentary Mode
In Momentary Mode, the
When first plugged in (or after power is lost and reapplied for any reason) the "memory" state is OFF. This means the unit will be OFF even if the front panel on/off rocker switch is on. It will stay off until sequenced on by a momentary connection of the REM IN terminal to +12V. The sequence starts on the rising edge of the signal.
The front panel START
The “memory” is independent of the front panel on/off rocker switch. This means that even if the unit is sequenced OFF by the rocker switch on the front panel, when the rocker switch is turned back on the unit will sequence back on — it will not be necessary to push the START
The front panel rocker is not the primary means of control in momentary mode, and should normally be left ON. It may be a useful secondary means of control in the rare case of having several
Because it is a
Multiple Units
You can use more than one
If multiple
The STATUS lines work the same in either mode. Each reflects the true state of the outlets of its unit, and is affected by both the “memorized” state and by the front panel rocker switch. A separate LED must be used to indicate the status of each
To take care of the case of having several
Holding the REM line high for at least 4 seconds (whether by an actual remote switch or by any unit's front panel switch) will force all units to the OFF state, which will put them back in sync. This is the only way to
This section covers the case of multiple units in parallel (all sequences initiate simultaneously). See “AC Relay Accessory
*Momentary mode switching is not available in