GE 2500 Auxiliary Controls on your Zoneline, Auxiliary Controls - Dip Switches, Instructions

Models: 2500 3500

1 28
Download 28 pages 8.15 Kb
Page 5
Image 5
Auxiliary Controls on your Zoneline.

Auxiliary Controls on your Zoneline.

www.GEAppliances.com

Auxiliary Controls – Dip Switches

The auxiliary dip switch controls are located behind the room cabinet, through an opening in the control panel.

Remove the room cabinet. See the To Remove the

Room Cabinet section.

The factory settings will be in the DOWN position.

The owner is responsible for checking switches

Dip Switches

and ensuring they are in the desired position.

 

Safety Instructions

Operating

UP

DOWN

ALLI2R (All Electric Heat) (3500 Series models only)

C:FAN CN (Cooling–Smart Fan)

H:FAN CY (Heating–Smart Fan) CLASS 2 (Remote Thermostat)

LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel)

CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)

1

2

3

4

5

6

7

8

1

2

3

HIGH

DOWN

COOL

UP

6

4

5

Auxiliary Controls – Dip SwitchesTL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)

TL1 (C) (Temp. Limit 1–Cool)

TL2 (C) (Temp. Limit 2–Cool)

TL3 (C) (Temp. Limit 3–Cool)

Instructions

Care and

All Electric Heat

This electric heat option functions only on the

 

3500 Series models. When this switch is enabled

 

(UP), heat pump operation is locked out, causing

 

the unit to provide only electric resistance heat.

ALLI2R (All Electric Heat)

Cooling–Smart Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When this switch is enabled (UP), it allows the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor fan to cycle on/off with the compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When this switch is disabled (DOWN), it allows

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the indoor fan to run continuously.

 

 

 

 

 

C: FAN CN (Cooling–Smart Fan)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating–Smart Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When this switch is enabled (UP), it allows the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor fan to run continuously. When this

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch is disabled (DOWN), it allows the indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan to cycle on/off with the heat pump or

 

 

 

 

 

 

 

 

H: FAN CY (Heating–Smart Fan)

 

heater operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Cleaning

Troubleshooting Tips