20
Installation Instructions
DUCTWORK CALCULATIONS

Calculate Total Equivalent Ductwork Length

Equivalent Number Equivalent
Duct Pieces Length* x Used = Length
6round
straight 1 ft. x ( )= ft.
314x 10
straight 1 ft. x ( )= ft.
6, 90°
elbow 15 ft. x ( ) = ft.
6, 45°
elbow 9 ft. x ( ) = ft.
24max.
flexible
metal offset
adapter 34 ft. x ( )= ft.
314x 10
90°elbow 16 ft. x ( ) = ft.
314
x 10
45°elbow 5 ft. x ( ) = ft.
314x 10
90°flat elbow
18 ft. x ( )= ft.
6round
to 314x 10
transition 7 ft. x ( ) = ft.
Subtotal Column 1 = ft.

*Equivalent lengths of duct pieces are based on

actual tests and reflect requirements for good

venting performance with any downdraft cooktop.

†Measure and list feet of straight duct used. Count

and list the quantity of all other duct pieces for the

“Number Used” of each type.

IMPORTANT:

For maximum efficiency, use the shortest and

straightest duct run possible, with as few fittings

as possible. For satisfactory performance, the duct

run should not exceed 100 feet equivalent length.

Venting performance is improved by using larger

diameter duct.

Equivalent Number Equivalent
Duct Pieces Length* x Used = Length
6round
to 314x 10
transition
90°elbow 20 ft. x ( ) = ft.
314x 10
to 6round
transition 5 ft. x ( ) = ft.
314x 10
to 6round
transition
90°elbow 12 ft. x ( )= ft.
6round
wall cap
with damper 21 ft. x ( ) = ft.
314
x 10
wall cap
with damper 27 ft. x ( ) = ft.
6round
roof cap 20 ft. x ( ) = ft.
6round
roof vent 24 ft. x ( ) = ft.
Subtotal Column 2 = ft.
Subtotal Column 1 = ft.
TOTAL DUCTWORK = ft.
Should not exceed 100 feet.

DO NOT use flexible plastic ducting.

Vent installation should not exceed 100 feet

equivalent length.