GE RAK164D1, RAK148D1 Turns on and stage 2 turns on, Adjust to calibrate displayed room

Models: RAK164D1 RAK148D1

1 16
Download 16 pages 45.41 Kb
Page 9
Image 9

3. Temperature Differential—Stage 2—(RAK148D1 only) (1–9°F) (1–5°C)—Set the number of degrees between when stage 1

turns on and stage 2 turns on.

Press the < or > button to set differential value. Press the SW6 button to advance to the next screen.

4. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)

Adjust to control the minimum Cool set temperature allowed. Press the < or > button to select.

Press the SW6 button to advance to the next screen.

5. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22, 23, 24, 26, 27, 29°C)

Adjust to control the maximum Heat set temperature allowed. Press the < or > button to select.

Press the SW6 button to advance to the next screen.

6.Room temperature offset (+9°F to –9°F) (+5°C to –5°C)

Adjust to calibrate displayed room

temperature to match actual room temperature. Press the < or > button to select.

Press the SW6 button to advance to the next screen.

9

Page 9
Image 9