3. Temperature
turns on and stage 2 turns on.
Press the < or > button to set differential value. Press the SW6 button to advance to the next screen.
4. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set temperature allowed. Press the < or > button to select.
Press the SW6 button to advance to the next screen.
5. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22, 23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set temperature allowed. Press the < or > button to select.
Press the SW6 button to advance to the next screen.
6.Room temperature offset (+9°F to –9°F) (+5°C to –5°C)
Adjust to calibrate displayed room
temperature to match actual room temperature. Press the < or > button to select.
Press the SW6 button to advance to the next screen.
9