GE RPS12 Installation in a Lighting Automation Panel, Basic Installation Steps, Wire, Volt

Models: RPS12

1 4
Download 4 pages 8.82 Kb
Page 3
Image 3
INSTALLATION

 

Catalog Number: RSP12

CAUTION: The power supply must be OFF when

both line-voltage and low-voltage sections. The line-

inserting or removing components. These instructions

voltage sections must be covered to avoid exposure to

assume the panel has a standard cover which exposes

live high-voltage wiring.

INSTALLATION

There are two recommended ways to install the RSP12 Remote Control Smart Sweeper — in a Lighting Automation Panel (LAP) or in an Accessory Cabinet near a Lighting Automation Panel

Installation in a Lighting Automation Panel

A complete LAP assembly includes the following TLC components:

Tub

RTUB12, -24 or -48

Cover

RCOV12xx, -24xxx or -48xxx

Interior

RINTER0012RC, -0024RC or -0048RC*

Power Supply

RPWRxxx

Relays

RR7P or RR9P

* RINTER0012RC and -0024RC accept one RSP12, RINTER0048RC accepts one or two

Details for assembling a complete Lighting Automation Panel are outlined separately in the RINTER installation instructions. Once the panel is assembled and relays are connected to the motherboard, the RSP12 may be installed.

Basic Installation Steps

1.Mount the RSP12(s) on the panel accessory bracket.

2.Wire 24V rectified power from the panel motherboard to the blue and white power input tabs on the RSP12.

3.Wire red and black connections for each relay from the panel motherboard to relay outputs on the RSP12.

4.Wire any 2- or 3-wire switch to the individual switch inputs and/or the Master switch input on the RSP12 (not on the panel motherboard).

5.Select additional control functions.

Installation in an Accessory Cabinet near the LAP

Accessory cabinets with covers include:

RBS1 Accepts one (1) RSP12

RBS2 Accepts two (2) RSP12s

Mount the RSP12 in the accessory cabinet and wire the same as above.

12-RELAY

LIGHTING

AUTOMATION

PANEL24-RELAY LIGHTING AUTOMATION PANEL

1. MOUNT RSP12 IN PANEL

48-RELAY LIGHTING

AUTOMATION PANEL

 

2.

18/2 AWG

 

 

 

WIRE

 

 

 

 

24 VOLT

 

 

 

 

RECTIFIED

 

24V

 

24V

 

 

 

 

POWER

 

RECT

PILOT

RECT

 

COMMON

 

 

BLUE

YELLOW

BLUE

 

 

 

 

24VRECT ACC

 

 

 

 

BLUE WHITE

24VAC COM

 

 

RSP12

 

 

 

 

 

 

 

ON TLC PANEL

 

 

 

 

MOTHERBOARD

Installation in a Lighting Automation PanelLOAD

CIRCUIT

RED BLACK YELLOW WHITE 1

RRxP RELAY

 

ON TLC PANEL

20/2 AWG

MOTHERBOARD

 

3.

 

 

RED

 

 

BLACK

WIRE

 

 

BLUE

RELAYS

RSP12

 

 

4. WIRE ANY 2- OR 3-WIRE SWITCHES

 

 

 

20/2 AWG 1000 FT. MAX.

 

 

 

 

RED

 

 

 

BLACK

 

 

 

WHITE

 

MAINTAINED

JUMP RED TO BLACK

RED

 

BLACK

 

ISOLATED

 

WHITE

 

CONTACT

 

RED

 

 

20/2 AWG 1000 FT. MAX.

BLACK

 

 

WHITE

 

 

 

 

 

 

RED

 

 

 

BLACK

 

 

JUMP BLACK TO WHITE

WHITE

 

 

RED

 

 

 

 

2-WIRE

 

BLACK

 

MOMENTARY

 

WHITE

 

PUSH BUTTON

 

RED

 

 

20/3 AWG 1000 FT. MAX.

BLACK

 

 

 

RSP12

 

 

WHITE

 

 

RED

 

 

 

 

 

BLACK

 

 

 

WHITE

 

 

 

RED

 

STANDARD

 

BLACK

 

3-WIRE

 

WHITE

 

MOMENTARY

 

RED

 

 

20/3 AWG 1000 FT. MAX.

BLACK

 

 

WHITE

 

 

 

 

 

 

RED

 

 

 

BLACK

 

 

 

WHITE

 

 

 

RED

 

STANDARD

 

BLACK

 

3-WIRE

 

WHITE

 

MAINTAINED

 

RED

 

 

 

BLACK

 

 

 

WHITE

 

Page 3
Image 3
GE RPS12 Installation in a Lighting Automation Panel, Basic Installation Steps, MOUNT RSP12 IN PANEL, Wire, Volt