Catalog Number: RSP12
ADDITIONAL CONTROL FUNCTIONS
Four optional control functions are available at the bottom of the RSP12 board: Occupied, Time Delay, Warn and Auto Off. Set these functions for all relays connected to the RSP12 as a group, based on the needs at the site.
Occupied
The Occupied contact is available for connection with a timeclock or building automation system. It indicates when the building is operating under normal working hours (CLOSED contact) or after hours (OPEN contact). Properly connecting and scheduling the Occupied contact determines when other functions will be enabled.
Time Delay
If the Time Delay function is set, when an occupant turns on a switch after hours (Occupied contact OPEN), the RSP12 will turn off the lights again after a predetermined amount of time. Each occupant override will have its own time delay.
Set the Time Delay dial as follows:
0No time delay (no automatic off; lights must be manually turned off)
9
Warn
When the RSP12 turns relays OFF (at the end of normal working hours, or at the end of a time delay), it will optionally warn the occupants by blinking the lights five minutes before they go off.
Set the WARN switch to YES or NO as follows:
YES Gives a
NO Turns lights off without giving the warning
Auto On
When the Occupied contact closes at the start of normal working hours, the RSP12 can optionally turn all the relays ON automatically.
Set the AUTO ON switch to YES or NO as follows:
YES Automatically turns all relays ON at start of normal working hours
NO Manual switch required to turn relays ON
EMERGENCY SERVICE OR SUPPORT:
| RSP12 |
|
|
OCCUPIED | 0 | WARN | AUTO ON |
YES | YES | ||
RED WHITE |
| NO | NO |
|
|
| |
| 20/2 AWG 1000 FT. MAX. | ||
|
|
| MAINTAINED ISOLATED CONTACT |
OCCUPIED CONTACT |
| IN TIME CLOCK (BY OTHERS) | |
|
| ||
| RSP12 |
|
|
OCCUPIED | 0 | WARN | AUTO ON |
YES | YES | ||
RED WHITE |
| NO | NO |
|
| 0 | |
|
|
|
TIME DELAY
0 | = NO TIME DELAY |
|
|
|
| |
1 | = |
|
|
|
| |
2 | = |
|
|
|
| |
3 | = |
|
|
|
| |
…ETC. TO… |
|
|
|
|
| |
8 | = |
|
|
|
| |
9 | = |
|
|
|
| |
|
|
|
| RSP12 |
|
|
|
| OCCUPIED | 0 | WARN | AUTO ON | |
|
| YES | YES | |||
|
| RED | WHITE |
| NO | NO |
|
|
|
|
| ||
| WARN | NO 1 |
|
|
|
|
| YES |
| WARN SWITCH | |||
| NO |
|
| |||
|
|
|
|
|
| |
|
|
|
| RSP12 |
| |
|
| OCCUPIED | 0 | WARN | AUTO ON | |
|
| YES | YES | |||
|
| RED | WHITE |
| NO | NO |
|
|
|
|
| ||
2 | AUTO ON |
|
|
| ||
YES |
| AUTO ON SWITCH | ||||
|
| |||||
| NO |
|
|
|
|
|