SCA2000BCC - GE Profile Performance™ Advantium™ Oven
Hood Exhaust Duct
Outside ventilation requires a HOOD EXHAUST DUCT. Read the following carefully.
EXHAUST CONNECTION:
The hood exhaust has been designed to mate with a standard
If a round duct is required, a
REAR EXHAUST:
If a rear or horizontal exhaust is to be used, care should be taken to align exhaust with the space between studs, or wall should be prepared at the time it is constructed by leaving enough space between the wall studs to accommodate exhaust.
MAXIMUM DUCT LENGTH:
For satisfactory air movement, the total duct length of
ELBOWS, TRANSITIONS, WALL AND ROOF CAPS, etc., present additional resistance to airflow and are equivalent to a section of straight duct which is longer than their actual physical size. When calculating the total duct length, add the equivalent length of all transitions and adaptors plus the length of all straight duct sections. The chart below shows the approximate feet of equivalent length of some typical ducts.
Duct | Equivalent | |
A. | 5 Ft. | |
| Transition Adaptor |
|
B. | Wall Cap | 40 Ft. |
|
|
|
C. | 90° Elbow | 10 Ft. |
|
|
|
D. | 45° Elbow | 5 Ft. |
Filter Kit Accessory
Grille
Filter Kit
To be used when the Advantium oven cannot be vented to the outside.
E. | 90° Elbow | 25 Ft. |
F. | 45° Elbow | 5 Ft. |
G. | Roof Cap | 24 Ft. |
For answers to your Monogram,®
GE Profile Performance Series,™
GE Profile™ or GE appliance questions, call
GE Answer Center® service, 800.626.2000.
Listed by
Underwriters
RLaboratories
Specification Revised 11/99