Generac 005030-0 (15kW) Generator Location, Generator Mounting Support, ‹ 2.1.1 Nfpa Standards

Models: 005030-0 (15kW) 005031-0 (25kW)

1 60
Download 60 pages 32.59 Kb
Page 11
Image 11

Section 2 — Installation

Liquid-cooled 15, 20 and 25 kW Generators

2.1STANDBY GENERATOR INSTALLATION

DANGER

Connecting this generator to an electrical sys- tem normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distri- bution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

If an open bottom is used, the engine-genera- tor must be installed over non-combustible materials and should be located such that com- bustible materials are not capable of accumu- lating under the generator set.

Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula- tions pertaining to the installation.

After the system has been installed, do nothing

!that might render the installation in noncompli- ance with such codes, standards and regula- tions.

NOTE:

For more information about the installation of a standby system contact an Authorized Service Dealer.

‹2.1.1 NFPA STANDARDS

The following published standards booklets pertain- ing to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:

NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.

NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-

TEMS FOR HEALTH CARE FACILITIES.

NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION

NFPA No. 68, GUIDE FOR EXPLOSION VENTING

NFPA No. 70, NATIONAL ELECTRICAL CODE.

NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.

NFPA No. 10, INSTALLATION, MAINTENANCE AND USE OF PORTABLE FIRE EXTINGUISHERS.

‹2.1.2 OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following infor- mation pertaining to the installation and use of standby electric systems is available:

Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.

AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.

ASAE EP-364.2, INSTALLATION AND MAINTE-

NANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.

A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYS- TEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y. 10018.

2.2GENERATOR LOCATION

Install the generator set, in its protective enclosure outdoors, where adequate cooling and ventilating air always is available. Consider these factors:

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift- ing, consider using a windbreak to protect the unit.

Install the generator on high ground where water levels will not rise and endanger it.

Allow sufficient room on all sides of the generator for maintenance and servicing. A required mini- mum allowance of space to any solid structure is three feet. Five feet allowance of space is recom- mended.

Where strong prevailing winds blow from one direction, face the generator air inlet openings into the prevailing winds.

Install the generator as close as possible to the transfer switch. This reduces the length of wiring and conduit.

Install the generator as close as possible to the fuel supply, to reduce the length of piping. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REG- ULATE THE DISTANCE.

2.3GENERATOR MOUNTING AND

SUPPORT

Retain the generator compartment to a concrete slab with 1/4-inch masonry type anchor bolts. Be sure the bolts are long enough to retain the compartment. The slab should be at least six inches thick and should extend beyond the enclosure to a distance of at least three inches on all sides.

9

Page 11
Image 11
Generac 005030-0 (15kW), 005031-0 (25kW) owner manual Generator Location, Generator Mounting Support, ‹ 2.1.1 Nfpa Standards

005030-0 (15kW), 005031-0 (25kW) specifications

Generac has long been recognized as a leader in backup power solutions, and its 005031-0 (25kW) and 005030-0 (15kW) home standby generators exemplify the brand's commitment to reliability and performance. Designed for residential use, these generators provide peace of mind during outages, ensuring that homes remain powered even in the most challenging conditions.

One of the standout features of both models is their advanced Generac G-Force engine, which is engineered for longevity and impressive power output. The G-Force engine is built from the ground up for generator use, refined to handle the unique demands of continuous operation. This results in a highly durable system that requires little to no maintenance, making it a favored choice for homeowners looking for a reliable energy solution.

Another important characteristic is the True Power technology featured in both generators. This technology delivers clean, stable power that is safe for sensitive electronics and appliances. It ensures that devices such as computers and medical equipment operate smoothly without the risk of damage from power fluctuations. Additionally, the Generac 005031-0 and 005030-0 generators are equipped with the Quiet-Test mode, allowing them to run at lower RPMs during routine weekly self-tests. This innovation significantly reduces the noise produced during tests, making it less disruptive for residents.

Furthermore, these generators come with a user-friendly interface and a mobile link app, enabling homeowners to monitor their generator's performance remotely via a smartphone. This feature enhances convenience, allowing users to receive alerts and notifications about their generator's status, maintenance needs, and operation conditions right from their devices.

Both the 25kW and 15kW models are also designed with a robust transfer switch, which seamlessly shifts power from the grid to the generator in case of any outages. This automatic transfer feature ensures that homes maintain power without needing manual intervention, making them ideal for those who want uninterrupted electricity.

In terms of fuel source, both models operate on natural gas or propane, providing flexibility to homeowners regarding fuel availability and preferences. With excellent warranty options and Generac's reputation for quality, both the 005031-0 (25kW) and 005030-0 (15kW) generators stand as dependable choices for safeguarding homes from the unpredictability of power outages.