Section 4 — Maintenance

Liquid-cooled 15, 20 and 25 kW Generators

5.Apply light coating of new engine oil to seal of new oil filter. Install FILTER and tighten by hand only.

DO NOT OVER TIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

After refilling the crankcase with oil, always

!check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

7.Start engine and check for oil leaks.

‹4.8.11 CHANGING THE ENGINE AIR CLEANER

To replace the engine air cleaner, (part number 059402), simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover (Figure 4.1).

See the “Service Schedule,” for air cleaner mainte- nance.

‹4.8.12 SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as necessary (Figure 4.4). See Section 6.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule,” Section 6, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.07-1.17 mm (0.042- 0.046 inch) by carefully bending the ground elec- trode (Figure 4.2).

Figure 4.4 – Setting the Spark Plug Gap

SET PLUG GAP AT 1.07 - 1.17 mm

(0.042 - 0.046 inch)

22

‹4.8.13 COOLANT CHANGE

Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See “Specifications” for cooling system recommenda- tions.

4.9MISCELLANEOUS MAINTENANCE

‹4.9.1 CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year have the generator cleaned and inspected by an Authorized Service Dealer. That deal- er will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹4.9.2 BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

Page 24
Image 24
Generac 005031-0 (25kW) Miscellaneous Maintenance, ‹ 4.8.11 Changing the Engine AIR Cleaner, ‹ 4.8.13 Coolant Change

005030-0 (15kW), 005031-0 (25kW) specifications

Generac has long been recognized as a leader in backup power solutions, and its 005031-0 (25kW) and 005030-0 (15kW) home standby generators exemplify the brand's commitment to reliability and performance. Designed for residential use, these generators provide peace of mind during outages, ensuring that homes remain powered even in the most challenging conditions.

One of the standout features of both models is their advanced Generac G-Force engine, which is engineered for longevity and impressive power output. The G-Force engine is built from the ground up for generator use, refined to handle the unique demands of continuous operation. This results in a highly durable system that requires little to no maintenance, making it a favored choice for homeowners looking for a reliable energy solution.

Another important characteristic is the True Power technology featured in both generators. This technology delivers clean, stable power that is safe for sensitive electronics and appliances. It ensures that devices such as computers and medical equipment operate smoothly without the risk of damage from power fluctuations. Additionally, the Generac 005031-0 and 005030-0 generators are equipped with the Quiet-Test mode, allowing them to run at lower RPMs during routine weekly self-tests. This innovation significantly reduces the noise produced during tests, making it less disruptive for residents.

Furthermore, these generators come with a user-friendly interface and a mobile link app, enabling homeowners to monitor their generator's performance remotely via a smartphone. This feature enhances convenience, allowing users to receive alerts and notifications about their generator's status, maintenance needs, and operation conditions right from their devices.

Both the 25kW and 15kW models are also designed with a robust transfer switch, which seamlessly shifts power from the grid to the generator in case of any outages. This automatic transfer feature ensures that homes maintain power without needing manual intervention, making them ideal for those who want uninterrupted electricity.

In terms of fuel source, both models operate on natural gas or propane, providing flexibility to homeowners regarding fuel availability and preferences. With excellent warranty options and Generac's reputation for quality, both the 005031-0 (25kW) and 005030-0 (15kW) generators stand as dependable choices for safeguarding homes from the unpredictability of power outages.