SPECIFICATIONS |
|
|
| ® | ||
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
GENERATOR |
| Model 05518 (8 kW) | Model 05520 (10 kW) | Model 05522 (14 kW) |
| |
Rated Maximum Continuous Power Capacity (LP) | 8,000 Watts* | 10,000 Watts* | 14,000 Watts* |
| ||
Rated Maximum Continuous Power Capacity (NG) | 7,000 Watts* | 9,000 Watts* | 13,000 Watts* |
| ||
Rated Voltage |
| 120/240 | 120/240 |
| 120/240 |
|
Rated Maximum Continuous Load Current |
|
|
|
|
| |
240 Volts |
| 33.3 LP/29.2 NG | 41.6 LP/37.5 NG | 58.3 LP/54.2 NG |
| |
Total Harmonic Distortion |
| Less than 5% | Less than 5% | Less than 5% |
| |
Main Line Circuit Breaker |
| 35 Amp | 45 Amp | 60 Amp |
| |
Phase |
| 1 | 1 |
| 1 |
|
Number of Rotor Poles |
| 2 | 2 |
| 2 |
|
Rated AC Frequency |
| 60Hz | 60Hz | 60Hz |
| |
Power Factor |
| 1 | 1 |
| 1 |
|
Battery Requirement (not included) | Group 26R | Group 26R | Group 26R |
| ||
|
| 12 Volts and | 12 Volts and | 12 Volts and |
| |
|
| 350 | 525 | 525 |
| |
|
| Amperes Minimum | Amperes Minimum | Amperes Minimum |
| |
Unit Weight |
| 340 Pounds | 387 Pounds | 439 Pounds |
| |
Dimensions (L” x W” x H”) |
| 48 x 25 x 29 | 48 x 25 x 29 | 48 x 25 x 29 |
| |
Sound output in dB(A) at 23 ft. with generator operating at normal load | 62 | 63 |
| 66 |
| |
ENGINE |
| Model 05518 (8 kW) | Model 05520 (10 kW) | Model 05522 (14 kW) |
| |
Type of Engine |
| GENERAC OHVI | GENERAC OHVI | GENERAC OHVI |
| |
Number of Cylinders |
| 1 | 2 |
| 2 |
|
Rated Horsepower |
| 14.8 @ 3,600 rpm | 18 @ 3,600 rpm | 32 @ 3,600 rpm |
| |
Displacement |
| 410cc | 530cc | 992cc |
| |
Cylinder Block |
| Aluminum w/Cast | Aluminum w/Cast | Aluminum w/Cast |
| |
|
| Iron Sleeve | Iron Sleeve | Iron Sleeve |
| |
Valve Arrangement |
| Overhead Valve | Overhead Valve | Overhead Valve |
| |
Ignition System |
|
| ||||
Governor System |
| Mechanical | Electronic | Electronic |
| |
Compression Ratio |
| 9.4:1 | 9.5:1 |
| 9.5:1 |
|
Starter |
| 12 Vdc | 12 Vdc | 12 Vdc |
| |
Oil Capacity Including Filter | Approx. 1.5 Qts. | Approx. 1.7 Qts. | Approx. 1.9 Qts. |
| ||
Operating RPM |
| 3,600 | 3,600 |
| 3,600 |
|
Fuel Consumption |
|
|
|
|
|
|
Natural Gas | cu.ft./hr. |
|
|
|
|
|
| 1/2 Load | 77 | 102 |
| 156 |
|
| Full Load |
|
| |||
| 139 | 156 |
| 220 |
| |
Liquid Propane | ft3/hr (gal/hr) |
|
| |||
|
|
|
|
| ||
| 1/2 Load | 34 (0.94) | 46 (1.25) |
| 58 (1.56) |
|
| Full Load | 62 (1.68) | 70 (1.93) |
| 84 (2.30) |
|
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas |
| |||||
CONTROLS |
|
|
|
|
|
|
Simple user interface for ease of operation |
|
| ||||
Mode Switch |
|
|
|
|
|
|
| Automatic Start on Utility failure. 7 day exerciser |
|
| |||
|
| Stops unit. Power is removed. Control and charger still operate. |
| |||
|
| Start with starter control, unit stays on. If utility fails, transfer to load takes place. |
| |||
Engine Start Sequence |
| Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration) |
| |||
Engine |
|
| 10 seconds |
|
| |
Engine |
|
| 1 minute |
|
| |
Starter |
| Starter cannot |
| |||
2.5 Amp Timed Trickle Battery Charger |
| Standard |
|
| ||
Automatic Voltage Regulator w/Overvoltage Protection |
| Standard |
|
| ||
Automatic Low Oil Pressure Shutdown |
| Standard |
|
| ||
Overspeed Shutdown |
|
| Standard, 72Hz |
|
| |
High Temperature Shutdown |
| Standard |
|
| ||
Overcrank Protection |
|
| Standard |
|
| |
Safety Fuse |
|
| Standard |
|
|
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).