Section 2 — Post Installation Start-up and Adjustments

Air-cooled 7 kW, 12 kW and 15 kW Generators

2.6ADJUSTING THE REGULATOR

(NATURAL GAS ONLY)

Although the generator has been factory set to pro- vide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.

If experiencing engine problems at high or full load conditions follow these steps. It will require a fre- quency meter to perform this procedure.

1. Turn off utility power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open posi- tion.

2. Allow the generator to start before loading the generator. Confirm the no-load frequency with the roof open and door off is set at 63-63.5 Hz. Transfer load to emergency circuits.

3. Turn on appliances, lights, pumps, etc., that are on the emergency circuits in an attempt to fully load the generator. Be cautious not to overload the generator. Use the following chart as a guide:

 

Unit

120 Volts

240 Volts

 

 

7 kW

50.0 amps

25.0 amps

 

 

12 kW

83.3 amps

41.6 amps

 

 

15 kW

108.3 amps

54.1 amps

 

 

 

 

 

 

4. When 3/4 load has been achieved. Connect a fre- quency meter to the output lugs of the generator’s main line circuit breaker.

5. The fuel regulator is fitted with one (7 kW), or two (12 & 15 kW) adjustment screws. While watching the frequency meter, slowly turn the adjustment screw clockwise or counterclockwise one at a time until highest frequency is read on the meter. Only limited adjustment is available between the set pins. Under no circumstances should any of the pins be removed (Figures 2.1 and 2.2).

Figure 2.1 — Dual Fuel Regulators

V-twin

410

Adjustment

Adjustment

Set

Screw

Screw

(One Side

Pin

(Both Sides)

Only)

 

 

 

Set Pin

(Both Sides)

12

6.When the highest frequency is reached maximum power has been set. Then turn both adjustment screws 1/4 turn counterclockwise. Regulator is now set.

Figure 2.2 — Placement of Regulator

Adjustment Screw

7.Turn utility power to the main distribution panel back on. This can be done by switching the ser- vice main breaker to the on or closed position. Allow the generator to shut down.

Do not make any unnecessary adjustments. Factory settings are correct for most applica- tions. However, when making adjustments, be careful to avoid overspeeding the engine.

If this procedure or equipment are not available, locate the nearest Authorized Dealer and they can perform the adjustments.

NOTE:

A service fee may be charged for this adjustment.

2.7ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:

‹2.7.1 7 KW UNITS

1.Loosen the governor clamp bolt (Figure 2.3).

2.Hold the governor lever at its wide open throttle position, and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).

3.Start the generator; let it stabilize and warm up at no-load.

4.Connect an AC frequency meter across the gen- erators AC output leads.

5.Turn the primary adjust screw to obtain a fre- quency reading of 61.5 Hz. Turn the secondary adjust screw to obtain a frequency reading of 62.5 Hz.

Page 14
Image 14
Generac 04674-2, 04673-2, 04675-3 Adjusting the Regulator Natural GAS only, Engine Governor Adjustment, ‹ 2.7.1 7 KW Units

04674-2, 04675-3, 04673-2 specifications

Generac, a prominent name in the power equipment sector, offers a range of reliable and efficient energy solutions, including the models Generac 04673-2, 04675-3, and 04674-2. These models are designed to meet diverse consumer needs, from residential applications to larger commercial setups, providing dependable backup power during outages.

The Generac 04673-2 is a standout home standby generator specifically engineered for residential use. It boasts an automatic operation feature, ensuring that power is restored within seconds of an outage. This model operates on a robust Generac engine, delivering a reliable power output that can support essential household appliances and systems, including HVAC units, refrigerators, and sump pumps. One of the main characteristics of this generator is its Quiet Test mode, which runs at a lower RPM to minimize noise while conducting weekly self-tests, ensuring that the system is always ready when needed.

Moving on to the Generac 04675-3, this model offers enhanced features tailored for users needing higher power output. With a larger capacity, it can handle more demanding power needs, making it suitable for larger homes or small businesses. The 04675-3 is equipped with advanced technologies, including the Mobile Link™ remote monitoring system, which enables users to check the status and performance of their generator from anywhere using a smartphone or computer. This connectivity empowers users with real-time information and alerts regarding their generator's operational performance.

The Generac 04674-2 model rounds out the trio, engineered for those who need a powerful standby generator with a slightly different configuration. It features the same robust engine as the other models, ensuring reliability and user-friendly operation. Its standout feature is the integrated transfer switch capability, which allows for seamless transfer of power from the grid to the generator without manual intervention. This model also supports various fuel types, providing flexibility depending on user preference and availability.

All three Generac models focus on safety and efficiency, incorporating features such as excellent ventilation systems, all-weather enclosures, and user-friendly control panels. They are designed for low maintenance, ensuring long-lasting performance without extensive upkeep. With Generac's commitment to innovation and quality, these generators offer peace of mind, enabling users to maintain their lifestyles and operations without interruption during power outages. Whether for home or business use, the Generac 04673-2, 04675-3, and 04674-2 models represent a reliable choice in emergency power solutions.