QT045
OPERATING DATA
|
|
| QT045 |
|
KW RATING |
|
| 45 |
|
|
|
|
|
|
ENGINE SIZE |
|
| 2.4 Liter |
|
|
|
|
|
|
GENERATOR OUTPUT VOLTAGE/KW - 60Hz |
| KW | AMP | CB Size |
120/240V, |
| 45 | 188 | 200 |
120/208V, |
| 45 | 156 | 175 |
120/240V, |
| 45 | 135 | 150 |
277/480V, |
| 45 | 68 | 80 |
|
|
|
|
|
GENERATOR LOCKED ROTOR KVA |
|
|
|
|
AVAILABLE @ VOLTAGE DIP OF 35% |
|
|
|
|
Single phase or 208/240 |
|
| 100 |
|
480V |
|
| 110 |
|
|
|
| ||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas | Propane | ||
|
| (ft3/hr.) | (gal/hr.) | cu ft/hr |
Exercise cycle |
| 102 | 1.11 | 40.4 |
25% of rated load |
| 194 | 2.12 | 77.1 |
50% of rated load |
| 373 | 4.07 | 148 |
75% of rated load |
| 520 | 5.67 | 206.3 |
100% of rated load |
| 720 | 7.86 | 286 |
|
|
|
|
|
ENGINE COOLING | ft3/min. |
|
|
|
Air flow (inlet air including alternator and combustion air) |
| 2,725 |
| |
System coolant capacity | US gal. |
| 3.0 |
|
Heat rejection to coolant | BTU/hr. |
| 173,000 |
|
Max. operating air temp. on radiator | °C (°F) |
| 60 (150) |
|
Max. ambient temperature | °C (°F) |
| 50 (140) |
|
|
|
|
|
|
COMBUSTION AIR REQUIREMENTS |
|
|
|
|
Flow at rated power 60 Hz | cfm |
| 144 |
|
|
|
|
|
|
SOUND EMISSIONS IN DBA |
|
|
|
|
Exercising at 7 meters |
|
| 61 |
|
Normal operation at 7 meters |
|
| 73 |
|
|
|
|
|
|
EXHAUST |
|
|
|
|
Exhaust flow at rated output 60 Hz | cfm |
| 429 |
|
Exhaust temp. at muffler outlet | °F |
| 1150 |
|
|
|
|
|
|
ENGINE PARAMETERS |
|
|
|
|
Rated synchronous RPM | 60 Hz |
| 3600 |
|
HP at rated KW | 60 Hz |
| 71 |
|
|
|
|
| |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS |
|
|
| |
Temperature Deration |
|
|
|
|
3% for every 10 °C above - °C |
| 25 |
| |
1.65% for every 10 °F above - °F |
| 77 |
| |
Altitude Deration |
|
|
|
|
1% for every 100 m above - m |
| 183 |
| |
3% for every 1000 ft. above - ft. |
| 600 |
| |
|
|
|
|
|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
KW rating is based on LPG Fuel and may derate with natural gas.