Standby Generator Sets

Specifications

SPECIFICATIONS

‹ GENERATOR

Type

Synchronous

Rotor Insulation

Class H

Stator Insulation

Class H

Total Harmonic Distortion

< 3.5%

Telephone Interference Factor (TIF)

< 50

Alternator Output Leads 3-phase

6-wire

Bearings

Sealed Ball

Coupling

Flexible Disc

Load Capacity (Standby Rating)

100kW*

*NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas.

Excitation System

 

Brushless

Generator Output Voltage/kW - 60 Hz

kW

Amp

CB Size

120/240V, 1-phase, 1.0 pf

100

417

500

120/208V, 3-phase, 0.8 pf

100

347

400

277/480V, 3-phase, 0.8 pf

100

150

200

Generator Locked Rotor KVA Available @ Voltage Dip of 35%

 

Single-phase or 208 3-phase

 

190

KVA

480V, 3-phase

 

225

KVA

‹ ENGINE

Make

Generac

Model

V-type

Cylinders and Arrangement

8

Displacement

5.4 Liter

Bore

3.55 in.

Stroke

4.17 in.

Compression Ratio

9-to-1

Air Intake System

Naturally Aspirated

Valve Seats

Hardened

Lifter Type

Hydraulic

Engine Parameters

 

Rated Synchronous RPM

60 Hz, 3600

HP at rated kW

60 Hz, 175

Exhaust System

 

Exhaust Flow at Rated Output 60 Hz

953 cfm

Exhaust Temperature at Rated Output

1000° F

Combustion Air Requirements (Natural Gas)

Flow at rated power, 60 Hz

325 cfm

Governor

 

Type

Electronic

Frequency Regulation

Isochronous

Steady State Regulation

± 1/2%

Adjustments:

 

Speed

Selectable

Engine Lubrication System

 

Type of Oil Pump

Gear

Oil Filter

Full Flow, Cartridge

Crankcase Oil Capacity

5 U.S. qts.

‹ COOLING SYSTEM

Type

Closed

Water Pump

Belt Driven

Fan Speed

1700

Fan Diameter

26 inches

Fan Mode

Puller

Air Flow (inlet air including alternator and

 

combustion air)

4800 ft3/min.

Coolant Capacity

(4.0 U.S. gal.)

Heat Rejection to Coolant

376,000 Btu/h

Maximum Operating Air Temp. on Radiator

60° C (150° F)

Maximum Ambient Temperature

50° C (140° F)

‹FUEL SYSTEM

Type of Fuel

...................................................................

 

Natural Gas

Carburetor

 

 

Down Draft

Secondary Fuel Regulator

 

Standard

Fuel Shut-off Solenoid

 

Standard

Operating Fuel Pressure

11 in. - 14 in. Water Column

Fuel Consumption - ft3/hr (Natural Gas/LPV)

Exercise

25%

50%

75%

100%

Cycle

Load

Load

Load

Load

140/56

371/149

713/287

994/400

1374/553

*Engine is not field convertible between natural gas and propane. Jet size and ignition timing are factory set for the specific fuel.

‹ELECTRICAL SYSTEM

Battery Charge Alternator

12V, 30 Amp

Static Battery Charger

12V, 2 Amp

Recommended Battery

24F 525CCA

System Voltage

12 Volts

Voltage Regulator

 

Type

Full Digital

Sensing

3-phase

Regulation

± 1/4%

Features

Built into H-100 Control Panel

 

V/F Adjustable, Adjustable

 

Voltage and Gain

Power Adjustment for Ambient Conditions

Temperature Deration

 

3% for every 10° C above °C

25

1.65% for every 10° above °F

77

Altitude Deration

 

1% for every 100 m above m

183

3% for every 1000 ft. above ft

600

Controller

H-panel

6-1

11/05 C .Rev GenSpec007

Page 10