Generac SD100 manual Operating Data, Standby, Prime

Models: SD100

1 4
Download 4 pages 27.15 Kb
Page 3
Image 3
OPERATING DATA

SD100

OPERATING DATA

 

 

 

 

 

STANDBY

 

 

PRIME

 

 

 

 

 

 

SD100

 

 

SD100

 

GENERATOR OUTPUT VOLTAGE/KW-60Hz

 

 

Rated AMP

 

 

Rated AMP

120/240V, 1-phase, 1.0 pf

 

 

100

 

 

417

 

91

 

379

120/208V, 3-phase, 0.8 pf

NOTE: Consult your

100

 

 

347

 

91

 

316

120/240V, 3-phase, 0.8 pf

Generac dealer for

100

 

 

301

 

91

 

274

277/480V, 3-phase, 0.8 pf

additional voltages.

100

 

 

150

 

91

 

137

 

 

 

 

 

 

600V, 3-phase, 0.8 pf

 

 

 

100

 

 

120

 

91

 

109

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR STARTING KVA

 

 

 

 

 

 

 

 

 

 

 

Maximum at 35% instantaneous voltage dip

208/240/416V

 

480V

208/240/416V

 

480V

with standard alternator; 60 Hz

 

206

 

 

275

 

206

 

275

 

 

 

 

 

 

 

 

 

 

 

 

FUEL

 

 

 

 

 

 

 

 

 

 

 

Fuel consumption—60 Hz

 

Load

25%

50%

75%

100%

25%

50%

75%

100%

 

 

 

gal./hr.

2.3

4.3

5.9

7.7

1.9

3.5

5.1

6.3

 

 

 

liters/hr.

8.7

16.2

22.4

29.0

7.1

13.3

19.4

23.9

Fuel consumption—50 Hz

 

gal./hr.

1.8

3.4

4.7

6.1

1.5

2.8

4.1

5.0

 

 

 

liters/hr.

7.0

12.9

17.9

23.2

5.7

10.6

15.5

19.1

Fuel pump lift

 

 

 

 

 

36"

 

 

 

36"

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING

 

 

 

 

 

 

 

 

 

 

 

Coolant capacity

System - US gal. (lit.)

 

5.5 (20.8)

 

 

5.5 (20.8)

 

 

 

Engine - US gal. (lit.)

 

3.75 (14.2)

 

 

3.75 (14.2)

 

Coolant flow/min.

 

60 Hz - US gal.

 

 

38

 

 

 

38

 

Heat rejection to coolant 60 Hz full load

BTU/hr.

 

 

280,000

 

 

252,000

 

Inlet air*

60 Hz - cfm (m3/min.)

 

7500 (212.4)

 

 

7500 (212.4)

 

Max. air temperature to radiator*

° C (°F)

 

60 (140)

 

 

60 (140)

 

Max. operating ambient temperature*

°C (°F)

 

50 (122)

 

 

50 (122)

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

 

 

 

 

 

Flow at rated power

 

60 Hz - cfm (m3/min.)

 

351 (10.0)

 

 

320 (9.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

 

 

 

 

 

 

 

 

 

 

 

Exhaust flow at rated output

60 Hz - cfm (m3/min.)

 

988 (28.0)

 

 

880 (24.9)

 

Max recommended back pressure Inches Hg

 

 

1.5

 

 

 

1.5

 

Exhaust temperature 60 Hz (full load)

°F (°C)

 

1050 (566)

 

 

990 (532)

 

Exhaust outlet size

 

 

 

 

4.0" O.D.

 

 

4.0" O.D.

 

 

 

 

 

 

 

 

 

 

 

 

 

ENGINE

 

 

 

 

 

 

 

 

 

 

 

Rated RPM

 

 

60 Hz

 

1800 / 1500

 

 

 

1800

 

HP at rated KW

 

 

60 Hz

 

158 / 122

 

 

144 / 99

 

Piston speed

60 Hz - ft./min. (m/min.)

 

1500 (457)

 

 

1500 (457)

 

BMEP

 

60 Hz / psi

 

 

248

 

 

 

225

 

 

 

 

 

 

 

 

 

 

 

 

 

DERATION FACTORS

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

-4.1% for every 10oC above - °C

 

 

40

 

 

 

40

 

-2.3% for every 10oF above - °F

 

 

104

 

 

 

104

 

Altitude

 

 

 

 

 

 

 

 

 

 

 

-0.8% for every 100 m above - m

 

 

1067

 

 

 

1067

 

-2.5% for every 1000 ft. above - ft.

 

 

3500

 

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

*Note: Values given are maximum temperatures to which power adjustments can be applied. Consult your Generac Power Systems representative if operating conditions exceed these maximums.

Page 3
Image 3
Generac SD100 manual Operating Data, Standby, Prime