Generac SD100 manual Application, Engineering Data, Engine Specifications, Voltage Regulator

Models: SD100

1 4
Download 4 pages 27.15 Kb
Page 2
Image 2
APPLICATION

APPLICATION

 

& ENGINEERING DATA

SD100

 

GENERATOR SPECIFICATIONS

 

ENGINE SPECIFICATIONS

TYPE

Four-pole, revolving field

ROTOR INSULATION

Class H

STATOR INSULATION

Class H

TOTAL HARMONIC DISTORTION

<3%

TELEPHONE INTERFERENCE FACTOR (TIF).

...............................<50

ALTERNATOR

Self-ventilated and drip-proof

BEARINGS (PRE-LUBED & SEALED)

1

COUPLING

Direct, Flexible Disc

LOAD CAPACITY (STANDBY)

100%

LOAD CAPACITY (PRIME)

110%

NOTE: Emergency loading in compliance with NFPA 99, NFPA 110. Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN6271 standards.

VOLTAGE REGULATOR

TYPE

Full Digital

SENSING

3 Phase

REGULATION

± 1/4%

FEATURES

Built into H-100 Control Panel, V/F Adjustable

 

Adjustable Voltage and Gain

GENERATOR FEATURES

Revolving field heavy duty generator

Quiet drive coupling

Operating temperature rise 120°C above a 40°C ambient

Insulation is Class H rated at 150°C rise

All prototype models have passed three phase short circuit testing

CONTROL PANEL FEATURES

TWO FOUR LINE LCD DISPLAYS READ:

Voltage (all phases)

Current (all phases)

Power factor

• kW

kVAR

Transfer switch status

Engine speed

• Low fuel pressure

Run hours

• Service reminders

Fault history

Oil pressure

Coolant temperature

• Time and date

• Low oil pressure shutdown

• High coolant temp shutdown

Overvoltage

• Overspeed

Low coolant level

Low coolant level

Exercise speed

• ATS selection

Not in auto position (flashing light)

INTERNAL FUNCTIONS:

I2T function for alternator protection from line to neutral and line to line short circuits

Emergency stop

Programmable auto crank function

2 wire start for any transfer switch

Communicates with the Generac HTS transfer switch

Built-in 7 day exerciser

Adjustable engine speed at exerciser

RS232 port for GenLink® control

RS485 port remote communication

Canbus addressable

Governor controller and voltage regulator are built into the master control board

Temperature range -40°C to 70°C

MAKE

GENERAC/DEERE

MODEL

See Exhaust Emission Sheet

ENGINE FAMILY

First digit is Cert. Yr. (i.e. 7, 8, 9) _JDXL06.8105

CYLINDERS

 

4

DISPLACEMENT

4.5 Liter (276 cu.in.)

BORE

106 mm (4.19 in.)

STROKE

127 mm (5.0 in.)

COMPRESSION RATIO

17:1

INTAKE AIR

Turbocharged/Aftercooled

NUMBER OF MAIN BEARINGS

5

CONNECTING RODS

4-Drop Forged Steel

CYLINDER HEAD

 

Cast Iron

PISTONS

4- Aluminum Alloy

CRANKSHAFT

Die Forged, Induction Hardened Steel

VALVE TRAIN

 

 

 

LIFTER TYPE

 

Solid

INTAKE VALVE MATERIAL

Heat Resistant Steel

EXHAUST VALVE MATERIAL

Heat Resistant Steel

HARDENED VALVE SEATS

Replaceable

ENGINE GOVERNOR

 

 

 

ISOCHRONOUS

 

Standard

FREQUENCY REGULATION, NO-LOAD TO FULL LOAD

..........0.5%

STEADY STATE REGULATION

0.25%

LUBRICATION SYSTEM

 

 

 

TYPE OF OIL PUMP

 

Gear

OIL FILTER

Full flow, Cartridge

CRANKCASE CAPACITY

22 qts.

COOLING SYSTEM

 

 

 

TYPE OF SYSTEM

Pressurized, Closed Recovery

WATER PUMP

Pre-Lubed, Self-Sealing

TYPE OF FAN

 

Pusher

NUMBER OF FAN BLADES

6

DIAMETER OF FAN

560 mm (22 in.)

COOLANT HEATER

120V, 1800 W

FUEL SYSTEM

 

 

 

FUEL

#2D Fuel (Min Cetane #40)

 

(Fuel should conform to ASTM Spec.)

FUEL FILTER

 

2 Micron

FUEL INJECTION PUMP

Denso

FUEL PUMP

 

Mechanical

INJECTORS

Multi-Hole, Nozzle Type

ENGINE TYPE

Direct Injection

FUEL LINE (Supply)

6.35 mm (0.25 in.)

FUEL RETURN LINE

6.35 mm (0.25 in.)

TOTAL FUEL FLOW

20.7 gal./hr.

ELECTRICAL SYSTEM

 

 

 

BATTERY CHARGE ALTERNATOR

65 Amps at 12 V

STARTER MOTOR

 

12 V

RECOMMENDED BATTERY

12 Volt, 135 A.H., 40CT

GROUND POLARITY

 

Negative

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with

BS5514, ISO3046 and DIN6271). Prime (Unlimited Running Time): Applicable for supplying electric power in lieu of commercially purchased power. Prime power is the maximum power available at variable load. A 10% overload capacity is available for 1 hour in 12 hours. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

Page 2
Image 2
Generac SD100 manual Application, Engineering Data, Engine Specifications, Voltage Regulator, Generator Features