1.7Specifications (DC/DC Power Models)
1.7.1Bridge/Multiplexer Models for DC/DC Power
Description | Name | BM85 Modbus Plus |
|
| Bridge/Multiplexer |
|
|
|
| Part Number | NW±BM85D002, NW±BM85D008 |
|
|
|
Mounting Method | Vertical | Standard 19 in Rack |
|
|
|
Physical | Height | 3.47 in (88 mm) |
Characteristics |
|
|
|
|
|
| Width | 19.00 in (483 mm), mounting panel |
|
|
|
|
| 18.26 in (464 mm), hole centers |
|
|
|
| Depth | 9.15 in (232 mm) |
|
|
|
| Weight | 5.5 lbs (2.5 kg) net |
|
|
|
|
| 6.5 lbs (3.0 kg) shipping |
|
|
|
Power | Requirements | 105 to 140 Vdc, or 24 Vdc +15% |
|
|
|
| Access | Rear panel screw terminals |
|
|
|
| Input Current | 0.41 A at 125 V dc |
|
|
|
| Inrush Current | 6 A typical at 125 V dc |
|
|
|
| Ground Leakage | 1 mA at 140 V dc |
|
|
|
| Fuse | External, customer supplied |
|
|
|
Environmental | Temperature | 0 ... 60 degrees C, operating |
|
|
|
|
| ±40 ... +80 degrees C, storage |
|
|
|
| Humidity | 0 ... 95%, non±condensing |
|
|
|
| Altitude | 10,000 ft (3 km), maximum |
|
|
|
| EMI, Radiated | 27 ... 500 mHz, 10 V/m |
| Susceptibility | IEC 801±3, level 3 |
|
| IEEE/ANSI C37.90.2, 1987 |
|
|
|
| Surge Withstand, | ± 2 kV (1 kV on I/O), V3300 |
| Fast Transient | generator into 50 ohms. |
|
| Corresponds to ± 4 kV (2 kV on I/O) |
|
| into open circuit. |
|
| IEC 801±4, level 3 |
|
| IEEE/ANSI C37.90.1 2.3, 1989 |
|
|
|
| Surge Transients | 2 kV |
|
| IEC 801±5, level 3 |
|
|
|
| Electrostatic Discharge | 8 kV, ten discharges |
|
| IEC 801±2, level 3 |
|
|
|
Surge Withstand, Oscillatory Wave
2.5kV
IEEE 472
IEEE/ANSI C37.90.1 2.2, 1989
14 Introducing the BM85 Bridge/Multiplexers | 31007492 |