3.4.6Link Timeout

The Purpose of the Parameter

Link timeout is the maximum time you will allow for a slave device to respond to a command issued at the BM85 Modbus slave port￿ In your application, if the timeout value is exceeded, a `slave device down` error code will be returned by the program function initiating the command to the device￿

If the timeout value is too short, slower devices may not have time to respond normally to their commands, resulting in apparent errors at the device￿ If the value is too long, and a device fails to respond, your application will have to wait until the timeout occurs before handling the device condition or using the port again￿

A value should be set to handle the slowest device at the port, without excessive delay￿ The value should accommodate the sum of the following:

Vserial communication time

Vslave device processing time: for example, controller scan time

VBM85 processing time for port transactions, approximately 4 ms￿

Setting the Parameter

You set each port's timeout parameter as a value in the range 1 ￿￿￿ 3000￿ The timeout value represents multiples of 100 milliseconds￿

For example, a parameter of 10 specifies a link timeout of 10 x 100 ms, or one second￿

32 Configuring the Modbus Models

31007492

Page 42