3.13 Modbus Port Indicator Codes

If the BM￿￿ detects a condition that prevents communication at its Modbus Plus or Modbus ports￿ it shuts off all ports and displays an error code pattern at its four Modbus port indicators￿

Indicator layouts are shown in Figure 22￿

The error pattern produces two ￿￿bit codes for two hexadecimal digits￿ First￿ the indicators show a steady pattern for one second￿ indicating the upper digit￿ Then they show a flashing pattern for one second with the lower digit￿ The continuous and flashing patterns alternate repetitively￿ Port ￿ is the most significant bit in each code￿

Indicators

Pattern

Hexadecimal Digit

4 ± 3 ± 2 ± 1

Steady

Upper digit

 

 

 

4 ± 3 ± 2 ± 1

Flashing

Lower digit

 

 

 

Hardware Error Codes: 11 ... 19 Hex

Code (Hexadecimal)

Meaning

11

PROM checksum error

 

 

12

RAM data test error

 

 

13

RAM address test error

 

 

14

Normal power down event

 

 

17

Bad or unexpected interrupt

 

 

18

EEPROM checksum error

 

 

19

Modbus port loopback error

 

 

Modbus Driver Error Codes: 24 ... 2E Hex

 

Code (Hexadecimal)

Meaning

 

 

 

 

24

Modbus transmit state error

 

 

 

 

25

Modbus receive state error

 

 

 

 

26

ASCII transmit communications state error

 

 

 

 

27

Transmit underflow error

 

 

 

 

28

RTU transmit communications state error

 

 

 

 

29

ASCII receive communications state error

 

 

 

 

 

2A

RTU receive communications state error

 

 

 

 

 

2B

Transmit communications state error

 

 

 

 

 

2C

Receive communications state error

 

 

 

 

54 Configuring the Modbus Models

31007492

Page 64
Image 64
Schneider Electric none Modbus Port Indicator Codes, Hardware Error Codes 11 .. Hex, Modbus Driver Error Codes 24 .. E Hex