Figure 3.2 — Engine Governor Adjustment

Section 3 — Operation

Guardian Liquid-cooled 27 kW and 30 kW Generators

6.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

Figure 3.2 — Engine Governor Adjustment

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

3.7WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load

LED1

2

U7

C4

C30

R25

R49

U1

.REV

E4906 PCB#

DIFFERENTIAL STABILITY

 

 

 

R44

 

C9

C27

Q2

 

 

 

 

 

 

J2

 

 

 

 

C26

 

 

 

 

D10

 

 

 

 

C21

 

C2

 

 

 

 

 

 

 

 

 

 

 

 

 

RL1

 

RL2

 

R1

 

 

 

 

R48

 

 

 

 

D17

 

 

 

 

 

 

 

J1

 

L3

 

 

 

 

 

 

 

D19

 

DIP SWITCH

 

1

UNUSED

POSITION 1

POSITION 2

3

50/60 HZ

GTS/ATS Select

 

 

2

GTS/ATS

ON = 50 HZ

ON = GTS

OFF = 60 HZ

OFF = ATS (standard mode)

4

50/60 HZ

 

 

to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

1.Place the AUTO/OFF/MANUAL switch in the AUTO position.

2.Press and hold the “Set Exercise” switch for three seconds, then release.

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in manual mode, or automatically start and run if UTILITY is lost while in Auto mode, but it will not perform a weekly exercise

3.5RETRANSFER AND SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as follows:

Verify that UTILITY power supply voltage to the transfer switch has been positively turned OFF, using whatever means provided (such as utility main line circuit breaker).

Set the generator’s main circuit breaker to its OFF or OPEN position.

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the AUTO/OFF/ MANUAL switch to OFF. Wait for engine to come to a complete stop.

For transfer to UTILITY position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the UTILITY power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

3.6AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

14 Generac® Power Systems, Inc.

cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switch to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

Figure 3.2 - “Set Exercise” Switch

 

 

S

 

 

 

S

 

FUSE

F

U

F

 

F

U

F

 

 

 

 

U

E

S

FUSE

E

S

4A

 

S

E

 

S

E

 

U

 

15A

 

UF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAT.

MAIN

CHARGER

 

 

AUTO

OFF

 

 

OFF

ON

 

SET

MANUAL

EXERCISE

 

TIME

 

Page 16
Image 16
Generac Power Systems 004988-1 owner manual 3.7WEEKLY EXERCISE CYCLE, 3.5RETRANSFER AND SHUTDOWN, 3.6AUTOMATIC OPERATION