Section 4 — Maintenance

Guardian Liquid-cooled 27 kW and 30 kW Generators

4.1MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

A. EVERY THREE MONTHS

1.Check battery state of charge and condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

B. ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

C. ONCE ANNUALLY

1.Test engine governor. Adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

D. FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 oper- ating hours or 6 months, whichever comes first.)

2.Retorque cylinder head. (See Torque Specs, Section 1.13.)

3.Retorque intake and exhaust manifold. (See Torque Specs, Section 1.13.)

4.3OVERLOAD PROTECTION FOR

ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

If a circuit breaker opens or a fuse element

!melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.

4.4CHECKING FLUID LEVELS

‹4.4.1 CHECK ENGINE OIL

Check engine crankcase oil level (Figure 4.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint-free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See Section 1.14 for recom- mended oils.

E.

EVERY 500 OPERATING HOURS

Figure 4.1 - Oil Dipstick and Oil Fill Cap

1.

Service air cleaner.

OIL

2.

Check starter.

3.

Check engine DC alternator.

DIPSTICK

4.2COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See Section 6 for installation drawings and vent locations.)

The exhaust system parts from this product get extremely hot and remain hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

OIL

FILL

‹4.4.2 BATTERY FLUID

Check battery electrolyte fluid at least once weekly. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

Generac® Power Systems, Inc. 15

Page 17
Image 17
Generac Power Systems 004988-1 Overload Protection for Engine DC Electrical System, Checking Fluid Levels, Cooling System

004988-1 specifications

Generac Power Systems has established itself as a leader in the generator industry, and the Generac Power Systems 004988-1 model exemplifies the company’s commitment to innovation, reliability, and performance. This standby generator is designed to provide seamless power solutions for both residential and commercial applications, ensuring that users remain connected and comfortable even during power outages.

One of the standout features of the 004988-1 model is its automatic transfer switch (ATS), which allows for instant power restoration within seconds of an outage. The ATS continuously monitors the electrical supply and automatically engages the generator when it detects a power failure, eliminating any stress or inconvenience for the user. This feature is particularly beneficial for those who may be away from home during an outage or for businesses that cannot afford downtime.

The 004988-1 is equipped with a powerful engine capable of delivering up to 20 kilowatts of backup power, sufficient to support essential household appliances and systems, such as HVAC, refrigeration, and lighting. Its robust construction ensures durability and longevity, equipped to withstand the rigors of extended use in various environmental conditions.

Another significant characteristic of this model is its emission-friendly design. Generac has incorporated advanced technologies to meet and exceed EPA standards, resulting in a cleaner and more environmentally friendly operation. The generator runs on natural gas or liquid propane, providing users with flexible fuel options and reducing dependency on traditional fuel sources.

Moreover, the 004988-1 comes with smart technology features, including Wi-Fi connectivity. This allows users to monitor and control their generator remotely via a smartphone app. Users can receive real-time notifications, monitor power usage, and conduct maintenance checks, ensuring peak performance of their generator.

The quiet operation of the 004988-1 is also noteworthy, making it an attractive option for residential areas where noise levels can be a concern. Generac has integrated sound-dampening technology, ensuring that the generator operates with minimal noise, allowing users to enjoy peace of mind without disruption.

In summary, the Generac Power Systems 004988-1 is a robust, reliable, and technologically advanced generator that seamlessly integrates into any household or commercial setup. With its automatic transfer switch, high power output, environmentally friendly design, smart technology features, and quiet operation, it stands out as an excellent choice for individuals seeking a dependable power solution for any situation.