6.7.2 WIRING
• Wiring should be of stranded copper to reduce the
chance that vibration may cause breakage.
• Wire gauge size should be large enough to handle at
least 115 percent of the installed generator's rated
maximum current.
If neutral conductors are used, they must be the same
size as other leg wires.
• Route power supply conductors from generator AC
output leads T1 (red), T2 (white), T3 (black) and the
green ground wire through approved flexible conduit
to the electrical junction box on the compartment
wall.
If flexible metal conduit is used between the genera-
tor and the compartment junction box, the conduit
end that terminates the compartment junction box
must be vapor-sealed. Flexible metal conduit is NOT
vapor tight along its entire length.
• From the junction box, route power supply wires
through approved conduit to either (a) double-pole,
double-throw transfer switch, or (b) approved isola-
tion receptacle. Connecting to a transfer switch or
isolation receptacle must prevent vehicle electrical
circuits from being connected to two different power
supplies at the same time (such as generator and
dockside power).
Conductors must be rated 221° F (105° C) or must be
of a larger conductor size.
6.7.3 GENERATOR AC CONNECTIONS
Generator AC output leads T1 (red), T2 (white) and T3
(black) come out of the generator as shown in Figure
2.17. Leads T1 (red) and T3 (black) are “hot,” while T2
(white) is the grounded neutral lead. There is also a
green lead that connects to ground in the junction box
of the recreational vehicle.

Figure 6.17 – Generator AC Output Leads

Line T1 (red) to T2 (white) is protected against overload
by a 20-amp circuit breaker (CB1). Use this line-to-neu-
tral connection separately to operate 120-volt, single-
phase, 60 Hertz, AC loads requiring up to 2,400 watts
(3.6 kW) of power. Line T3 (black) to T2 (white) also is
protected against overload by a 30-amp circuit breaker
(CB2). Use this line-to-neutral connection separately to
operate similar loads. However, be sure the total unit
load does not exceed the maximum rating of the gener-
ator. The neutral line (T2, white) on all units is a
grounded neutral.
Do NOT connect electrical loads in excess of any
circuit breaker rating or you will develop prob-
lems with circuit breaker tripping, which causes a
loss of AC output. Also, do NOT exceed the gener-
ator's rated wattage capacity. Add the watts or
amperes of all lighting, appliance, tool and motor
loads the generator will operate at one time. This
total should be less than the unit's rated
wattage/amperage capacity.
6.7.4 CONDUIT
Route the connections between the generator and the
junction box through approved, flexible conduit. The
following general rules apply:
Cut wiring to the required length and allow extra wire
for junction box connections.
• Carefully prepare conduit ends to prevent sharp
edges from cutting through wiring insulation.
• Route conduit so it does not interfere with generator
movement.
• If you use metallic conduit, vapor seal the end of the
conduit where it enters the junction box. Do this
because flexible metallic conduit is not vapor proof
along its entire length.
6.7.5 ISOLATING DIFFERENT POWER SOURCES
Connections from the junction box must terminate in a
double-pole, double-throw transfer switch (Figure 2.18,
Page 33). An alternate method for isolating different
power sources is by using an isolating receptacle
(Figure 2.19, Page 33). Whichever method you use, you
must be certain that both power sources are NOT con-
nected at the same time.