Standby Generator Sets

Maintenance

Figure 10.1 - Oil Dipstick and Oil Fill Cap

OIL FILL CAP

OIL

DIPSTICK

‹BATTERY FLUID

Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap (only when engine has cooled down) to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact a Service Dealer. Inspect cooling system and coolant recovery sys- tem for leaks.

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. For more detailed exercise information, see the respective sec- tions in the Control Panel Technical Manual that is supplied with the unit.

‹INSPECT COOLING SYSTEM

Inspect engine cooling system. See “Maintenance Schedule”.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels”.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

MAINTENANCE OWNER/OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels”.

‹CHECK BATTERY

See “Checking Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

06/07 D .Rev Maint011

10-2

Page 17
Image 17
Generac Power Systems 25, 20, 30 ‹ Battery Fluid, ‹ Exercise System, ‹ Inspect Cooling System, ‹ Check Engine Coolant Level

25, 30, 20 specifications

Generac Power Systems is a leading manufacturer of backup power generation products and tools, known for their reliability and innovation. Among their diverse lineup are the Generac 20kW, 25kW, and 30kW home standby generators. These models are designed to provide seamless power during an outage, allowing homeowners to maintain their everyday activities without interruption.

The Generac 20kW generator is particularly popular for residential use. It can power essential circuits as well as larger appliances, making it an ideal choice for homes with moderate electricity needs. One of its standout features is the Smart Management Module, which allows homeowners to manage energy consumption effectively, ensuring that they can run necessary appliances without overwhelming the system. Additionally, the 20kW generator is equipped with a durable enclosure, offering long-lasting protection against the elements.

Moving up in capacity, the Generac 25kW model caters to homes with higher electricity demands. This generator combines efficiency with strength, providing enough power for a wider range of home appliances and systems. It features a TruePower Technology that delivers clean power, crucial for sensitive electronics. Moreover, the 25kW model operates quietly, contributing to a comfortable home environment even during power outages.

The Generac 30kW generator is designed for larger homes or light commercial applications. It provides an impressive power output while maintaining high efficiency. Its features include advanced digital control, allowing for easy monitoring and maintenance. The 30kW model also offers an automatic transfer switch, which ensures that power is restored quickly and safely when utilities fail.

All three models utilize Generac's G-Force engine, known for its low maintenance requirements and high performance. They come with a five-year limited warranty, providing peace of mind for users. Furthermore, with Wi-Fi monitoring capabilities, homeowners can keep track of their generator's status from anywhere, ensuring they are always prepared for any power interruption.

In summary, the Generac 20kW, 25kW, and 30kW generators are excellent options for homeowners seeking reliable backup power. Their advanced features, durable construction, and efficient operation make them stand out in the market. Whether for essential home use or larger applications, Generac's lineup delivers dependable performance and innovative technology.