Gentek CO1209 Using The Reset Feature, Troubleshooting Guide, Maintenance

Models: CO1209

1 8
Download 8 pages 44.32 Kb
Page 7
Image 7
USING THE RESET FEATURE

USING THE RESET FEATURE

￿ The reset feature is for your convenience only and will not

correct a CO problem. ALWAYScheck your home for a

potential problem after any alarm. Failure to do so can result

in injury or death.

 

 

 

 

￿ NEVER remove the battery from your alarm to silence the

horn; use the reset feature. Removing the battery, removes

your protection! See “If Your CO Alarm Sounds” for details

on responding to an alarm.

 

 

 

The reset feature is intended to reset the CO alarm while the

problem is corrected - IT WILL NOT CORRECT A CO PROBLEM.

While the alarm has been reset, the device will continue to monitor

the air for the presence of CO.

 

 

 

When CO reaches alarm levels, the alarm will sound a repeating

temporal 4 repeating horn pattern - 4 beeps, a pause, 4 beeps, a

pause, etc. Press the reset button until the horn becomes silent.

The initial reset cycle will last approximately 5 minutes.

NOTE: After initial 5 minute reset cycle, the alarm will re-evaluate

present CO levels and respond accordingly. If CO levels remain

potentially dangerous, or increase to higher levels, the alarm will

sound again.

 

 

 

 

 

While the alarm is silenced:

 

 

 

If the CO alarm:

 

This means:

Is silent for only 5 minutes,

CO levels are still

then the alarm sounds again

potentially dangerous

If the CO alarm:

 

This means:

Remains silent after the test

CO levels are dropping

button has been pressed

 

 

 

 

TROUBLESHOOTING GUIDE

 

 

 

PROBLEM:

 

THIS MEANS:

ACTION TAKEN:

 

 

 

 

 

IF YOU ARE

 

 

 

 

 

FEELING

 

 

 

 

 

SYMPTOMS OF CO

 

CO alarm goes back

CO levels indicate

POISONING,

 

EVACUATE your home

 

into alarm 5 minutes

a potentially

and call 911 or the Fire

 

after the reset button

dangerous situation.

Department. If not,

 

was pressed.

 

 

 

press the reset button

 

 

 

 

 

again and keep

 

 

 

 

 

ventilating your

 

Green light is OFF. Red

Device may not be

home.

 

Contact licensed

 

light is not flashing.

 

Unit will not go into test

receiving power.

electrical technician for

 

mode when test button

NO AC and no

equipment inspection

 

is pressed.

 

battery in device.

service, immediately.

 

Alarm sounds 2 quick

Device has become

Clean (refer to

 

dirty or defective or

 

chirps every 30

 

large influx of CO

Maintenance Section)

 

seconds.

 

(over 1,000 ppm).

or warranty return.

 

Alarm sounds 3 quick

END OF LIFE

Contact Gentex

 

SIGNAL.

Device

Corporation for

 

chirps every 30

 

needs to be

replacement

 

seconds.

 

replaced.

 

information.

 

Green light is ON and

Low or no battery in

Replace battery (refer

 

red light is not flashing

device

 

to Battery Installation

 

and Alarm chirps once

AC is powering

Section) or return to

 

every 30 seconds

device

 

manufacturer

 

Reset button is

 

Device is not

Contact Gentex

 

pressed. LED’s do not

Corporation for

 

flash and device does

operating properly.

replacement

 

not go into test mode.

 

 

information.

 

Any questions that are

not answered within this manual, call Gentex

 

Corporation at 1-800-436-8391.

 

 

 

MAINTENANCE

DO NOT open CO alarm for cleaning. IF CO ALARM IS OPENED, PRODUCT WARRANTY BECOMES VOID.

CAUTION: If the device does not work properly, do not try and fix it yourself. This will void your warranty. See "TO RETURN A CO ALARM" for instructions to return CO alarms that do not operate properly. DO NOT TRY TO FIX IT YOURSELF.

Gentex recommends CO alarms be tested a minimum of once a week. The test feature of your CO alarm accurately simulates CO conditions and tests the CO alarm's functions as required by Underwriters Laboratories.

NOTICE: Do not cover, tape, or otherwise block the openings of your CO alarm. These openings are designed to allow air to pass through your CO alarm, thus sampling the air around the CO alarm. NOTICE: CO alarms are not to be used with detector guards unless the combination has been evaluated by a nationally recognized testing laboratory and found suitable for that purpose.

WEEKLY TESTING

Press the test/reset button on the alarm until the alarm sounds. During testing the device will simulate a CO condition in the alarm.

The alarm sequence should last 5-6 seconds. If the device does not go into alarm mode when tested, replace the device immediately.

￿ If the alarm ever fails to test properly, replace it immediately.

Products under warranty may be returned to the manufacturer for replacement, see “Limited Warranty.”

￿ DO NOT stand close to the device when the alarm is sounding. Exposure at close range could result in hearing damage.

￿ Never use exhaust from vehicle to test CO portion of alarm.

Exhaust may cause permanent damage to alarm and voids the warranty.

TO KEEP THE ALARM WORKING PROPERLY: ￿ Test weekly as described in “Weekly Testing.”

￿ Keep alarm cover clean using soft cloth. DO NOT vacuum or use compressed air, water, cleaners or solvents to clean alarm.

￿ Replace battery immediately if low battery warning is heard. See “Battery Installation” section.

NOTICE: DO NOT spray cleaning chemicals or insect sprays directly on or near the alarm. DO NOT paint over the alarm. Doing so may cause permanent damage.

￿ Household cleaners, aerosol chemicals and other contaminants can affect the sensor. When using any of these materials near the alarm, make sure the room is well ventilated.

￿ The CO alarm is not washable. DO NOT submerge the alarm in water. Water can affect the sensor, causing permanent damge.

￿ If your home is being fumigated, disconnect unit temporarily from wire harness and store where it will not be exposed to chemicals or fumes. When fumigation is complete and all traces of fumes clear, re-connect unit back to wire harness and push the reset button.

UNDERWRITERS LABORATORIES, INC. UL 2034 WHAT LEVELS OF CO CAUSE AN ALARM

UL Standard UL 2034 requires residential CO alarms to sound when exposed to levels of CO and exposure times as described below. CO levels are measured in part per million (ppm) of CO over time (in minutes).

UL 2034 Required Alarm Points1:

￿ If the CO alarm is exposed to 400ppm of CO, THE DEVICE MUST ALARM BETWEEN 4 - 15 MINUTES.

￿ If the CO alarm is exposed to 150 ppm of CO, THE DEVICE MUST ALARM BETWEEN 10 - 50 MINUTES.

￿ If the CO alarm is exposed to 70 ppm of CO, THE DEVICE MUST ALARM BETWEEN 60 - 240 MINUTES.

The device is designed not to alarm when exposed to a constant level of 30 ppm for 30 days.

1 Approximately 10% COHb exposure at levels of 10% to 95% Relative Humidity (RH).

550-0498 Pg. C-7

Page 7
Image 7
Gentek CO1209 installation instructions Using The Reset Feature, Troubleshooting Guide, Maintenance