4.A field
1.Attach a "jumper"wire across the two terminals of the sensor wires (see wiring diagrams on pages 11 through 14 showing the sensor being wired to the =COM" terminal of the defrost control board).
=Attach a "jumper" wire across the two "TST" terminals. The timing cycles are divided by a factor of 256. (e.g. 90 minutes is reduced to 21.1 seconds, 60 minutes to 14 seconds and 30 minutes to 7 seconds). At "T1" setting the unit should go into defrost in 7 seconds.
1For this test, the unit will stay in "defrost" for only about 2 to 3 seconds due to the 10 minute override. (L_. = 2.3 seconds)
°°° | TST | HLD | 24V OUT COM (_) |
| H | flfl H | |
0 |
| 0 |
|
T3 | T2 | T1. |
|
|
| JUMPER WIRE |
FIGURE 3
T3 = 90, T2 = 60, T1 = 30