PRODUCT SPECIFICATIONS
SPECIFICATIONS
Cooling Capacity
Total BTU/h | 86,000 | 86,000 | 116,000 | 116,000 |
Sensible BTU/h ¹ | 63,600 | 63,600 | 85,000 | 85,000 |
EER ² | 10.3 | 10.3 | 10.3 | 10.3 |
IPLV ³ | 10.7 | 10.7 | 10.7 | 10.7 |
Indoor Blowers (2) |
|
|
|
|
Type | Belt | Belt | Belt | Belt |
Wheel (D x W) | 12” x 12” | 12” x 12” | 12” x 15” | 12” x 15” |
Indoor Nominal CFM | 3,000 | 3,000 | 3,800 | 3,800 |
Horsepower | 1½ | 1½ | 3 | 3 |
Evaporator Coil (1) |
|
|
|
|
Face Area (ft²) | 11.2 | 11.2 | 14 | 14 |
Rows Deep/ Fins per Inch | 3/ 16 | 3/ 16 | 3/ 16 | 3/ 16 |
Tube Diameter - Material | ⅜” - Copper | ⅜” - Copper | ⅜” - Copper | ⅜” - Copper |
Filter Size (ft²) / Quantity | 16 x 25 x 2 / 3 | 16 x 25 x 2 / 3 | ||
| 25 x 25 x 2 / 3 | 25 x 25 x 2 / 3 | 20 x 25 x 2 / 3 | 20 x 25 x 2 / 3 |
Condenser Fans (2) / Coil (1) |
|
|
|
|
Horsepower | ½ | ½ | ½ | ½ |
Fan Diameter | 24” | 24” | 24” | 24” |
Outdoor Nominal CFM | 5,500 | 5,500 | 6,400 | 6,400 |
Face Area (ft²) | 15.6 | 15.6 | 23.8 | 23.8 |
Rows Deep/ Fins per Inch | 2/ 21 | 2/ 21 | 2/ 21 | 2/ 21 |
Tube Diameter - Material | ⅜” - Copper | ⅜” - Copper | ⅜” - Copper | ⅜” - Copper |
Electrical Data |
|
|
|
|
Compressor RLA/ LRA | 12.5/ 88 | 5.9/ 44 | 17.4/ 123 | 6.8/ 49.5 |
Indoor Blower FLA | 4.2 | 2.0 | 8.4 | 4.2 |
Outdoor Blower FLA | 2.6 | 1.3 | 2.6 | 1.3 |
Min. Circuit Ampacity 4 | 38.1 | 18.2 | 54.5 | 22.5 |
Max. Overcurrent Device 5 | 60 amps | 30 amps | 70 amps | 35 amps |
Operating Weight (lbs) | 980 | 980 | 1,270 | 1,270 |
Ship Weight (lbs) | 1,000 | 1,000 | 1,290 | 1,290 |
¹Sensible capacity is gross, with no deduction for indoor motor heat ² BTU/Watt @ 80/ 67° F inside; 95° F outside air
³ IPLV = Integrated Part Load Valve
4Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
5HACR breakers may be used in place of fuses up to 60 amps